Troubleshooting After Start
Use the actions suggested in this table if problems occur after the UPS is
started.
Table 6-2
Troubleshooting Guide (After Start)
Symptom
Possible Cause
Suggested Action
Indicators:
LINE STATUS
(flashing)
Alarm:
1 per minute
(can be
silenced)
UPS in STANDBY Mode.
Press and hold the ON/STANDBY
button for 2 seconds until you
hear a beep to switch UPS to
ON Mode.
Indicators:
ON BATTERY
BATTERY
LOW/REPLACE
Alarm:
continuous
(cannot be
silenced)
Battery voltage is low. Automatic
shutdown is imminent.
Immediately shut down
connected equipment.
Indicators:
UPS LOAD
Alarm:
none
Output:
none
Extreme overload condition
existed. Battery-protected devices
are exceeding the UPS power
rating. The UPS has automatically
shut down.
Remove excess load as quickly
as possible.
Press TEST/ALARM RESET
button to initiate self-test and
reset the UPS.
6-3