COMPARATO NELLO SRL

2

DIAMIX PR / COMPAMIX PR

NOTICES

 

This manual is an integral part of the product and shall be kept by the user. Read the warnings contained in the manual carefully, since they provide important information about safe installation, use and main-
tenance. Installation and maintenance shall be performed in accordance with the relevant regulations and the manufacturer's instructions. In case of failure and/or malfunctioning of the appliance, do not 
attempt any repair or direct servicing. Always contact qualified personnel, as provided by law. Only qualified technicians are allowed to carry out any repair operation. Failure to comply with the provisions 
listed above may compromise the safety of the appliance.  

 

 

OPERATION

 

DIAMIX PR 

and

 COMPAMIX PR

 motorised electronic mixing valves are used in modern heating and/or cooling systems equipped with floor, wall or ceiling radiating panels for the control of the delivery 

temperature and the dehumidification system: by exploiting the new functionalities they are able to keep under control the relative humidity inside the house and guarantee the maximum efficiency and the 
maximum environmental comfort. Their design fits multiple installation applications: once installed in the system, it is possible to select the type of operation of the motorised valve, enabling or disabling 
the various functions.  

• 

 

 

Fixed-point heating regulation 

  

Outlet temperatures for winter heating is set by means of the actuator keyboard and display. When the room thermostat activates the motorized valve, it acts in order to maintain the outlet temperature constant 
with an accuracy of +/-1°C.  

Heating system with climatic function 

 

The software automatically calculates the flow temperature to the heating “Tset_point” according to the external temperature detected by the relevant sensor (optional, code RFSONDAT) following programmable 
climatic curves.  

Tset_point = - (T_est * h1) + h2    where: 

T_est = temperature measured by the external sensor.  

h1 = angular coefficient of the adjustable curve between 0.1 and 1.0.  

h2 = temperature constant adjustable b30°C and +40°C.

DANGER:

DANGER:

Notices

  ___________________________________________________________________________ 

Operation

 ________________________________________________________________________ 

Remote management

 ______________________________________________________________________________________________ 

Features of the actuator

  _______________________________________________________________________________________________ 

Features of the ball valve

 __________________________________________________________________________ 

Installation

 __________________________________________________________________________ 

Electrical connections

 __________________________________________________________________________ 

Installation example

 __________________________________________________________________________ 

Keyboard and display

 __________________________________________________________________________ 

Activation and programming

 __________________________________________________________________________ 

Display alarms

 __________________________________________________________________________ 

Software reset

 __________________________________________________________________________ 

Accessories

 _______________________________________________________________________________________________________ 

General warranty conditions

 __________________________________________________________________________

INDEX

2

 

 

3

 

3

 

4

 

5

 

7

 

8

 

9

 

9

 

15

 

15

     

15

 

17

 

 
 

OUTLET TEMPERA

TURE T

setclim [°C]

EXTERNAL TEMPERATURE Test [°C]

Example with h1 = 0,5

During winter heating, the Tset_point value is bound to a temperature range of [+25°C; +45°C].  

Note: the system reads the external temperature every 30 minutes.  

Fixed-point cooling regulation 

 

The outlet temperature for summer cooling is set by means of the actuator keyboard and display. When the room thermostat activates the motorized valve, it acts in order to maintain the outlet temperature 
constant with an accuracy of +/-1°C. If the relative humidity and ambient temperature sensor (optional, code RFTRUEE10) is connected, if the difference between the calculated dew-point temperature and the 
delivery temperature to the system is lower than the set reference value “CF2”, the motorised valve activates a special alarm by closing a digital contact and displaying a signal (ALc). Moreover, the relative 
humidity value is constantly monitored and compared to a programmable reference value “CF1”: if the threshold value is exceeded, the motorised valve activates a special alarm by closing a digital contact and 
sending a signal to the display (ALur).  

CAUTION: this configuration requires a relative humidity adjustment system in the air-conditioned rooms independent of the mixing valve.

Electrical hazard!

 The unit contains high-voltage equipments.

Scalding hazard!

  Even in normal operation conditions, the unit can reach very high temperatures which may cause scalds.

Summary of Contents for Compamix PR

Page 1: ...VER 0 20 ...

Page 2: ...________ Features of the actuator _______________________________________________________________________________________________ Features of the ball valve __________________________________________________________________________ Installation __________________________________________________________________________ Electrical connections _________________________________________________________...

Page 3: ...g cooling adjustment The delivery temperature Tset_point for cooling is automatically calculated by the software as a function of the dew point temperature The dew point temperature is calculated by means of the relative humidity and ambient temperature sensor optional cod RFTRUEE10 T_setpoint Trugiada CI3 where Trujade Dew temperature calculated from relative humidity and ambient temperature CI3 ...

Page 4: ...617N 4 ROD BRASS CW617N 5 BALL SEAL P T F E 6 SEAL P T F E 7 O RING FKM 1 BODY BRASS CW617N 2 COUPLING BRASS CW617N 3 BALL CHROMED BRASS CW617N PTL 4 ROD BRASS CW614N 5 BALL SEAL P T F E 6 SEAL P T F E 7 O RING EPDM with union with union values referring to the most disadvantaged way L values referring to the most disadvantaged way L Code DN Δp max bar PN Connections Mixing KvS m3 h 20 G 3 4 16 16...

Page 5: ...Mounting the actuator facing downwards is not allowed Once installed the actuator connection should not be at the bottom of the valve SUBMERSIBLE OUTLET TEMPERATURE SEENSOR As an alternative to the cuff sensor the immersion sensor is available as an option It must be placed on the temperature controlled outlet M or AB using a G3 8 female well not included The sensor is fitted with a connector for ...

Page 6: ...RETURN RADIANT SYSTEM RETURN RADIANT FLOW FROM PRIMARY SYSTEM VALVE POSITION COMPLETELY HOT DIAMIX PR COMPAMIX PR 6 COMPARA TO NELLO SRL DIAMIX PR COMPAMIX PR LINE MIXED DIAMIX PR ISO 5211 CONNECTION DIAMIX PR ISO 5211 CONNECTION FLOW FROM PRIMARY SYSTEM FLOW FROM SYSTEM PRIMARY SYSTEM RETURN RADIANT SYSTEM RETURN RADIANT OUTLET MIXED OUTLET MIXED VALVE POSITION COMPLETELY HOT A AB B ...

Page 7: ...VDC POWER SUPPLY CABLE 5 x 0 5mm 2 SIGNAL CABLE 15 x 0 5mm 2 DIGITAL OUTLETS DIGITAL INLETS OUTDOOR TEMPERATURE PROBE ANALOG INPUT RELATIVE HUMIDITY AMBIENT TEMPERATURE PROBE MIXED TEMPERATURE PROBE RS485 Modbus RTU 230V 50 60 Hz 24V 50 60 Hz PUMP CONTROL Max 250V 1A D D PHASE NEUTRAL TEMPERATURE AND RELATIVE HUMIDITY SENSOR RFTRUEE10 INTEGRATION 24V DC CONTROL RELAY SUMMER WINTER CONTROL RELAY 24...

Page 8: ...sensor connector Room temperature probe Temperature probe Temperature probe RS485 Analog input RADIANT HEATING SYSTEM WITH EXTERNAL TEMPERATURE SENSOR FOR CLIMATIC FUNCTION HOUSING UNIT HEATING COOLING SYSTEM RADIANT WITH UMIDITY CONTROL BY MEANS OF A DEHUMIDIFIER SUPPLIED WITH REFRIGERATED WATER AT LOW TEMPERATURE INSTALLATION EXAMPLES 1 Hydraulic compensator 2 System pump 3 Room thermostat 4 Ext...

Page 9: ...YSTEM RADIANT WITH UMIDITY CONTROL BY MEANS OF A DEHUMIDIFIER SUPPLIED WITH REFRIGERATED WATER FOR RADIANT PANELS RED LED GREEN LED A Down arrow key B Up arrow key C Enter key D ON OFF key CAUTION Carry out the appropriate programming described in the following paragraphs in order to have the equipment working according to the type of system installed 1 Diverter motorised valve 2 Hydraulic compens...

Page 10: ...tive humidity of air conditioned environment d xx calculated dew point temperature I xx system flow temperature fixed point heating mode winter C xx system flow temperature climate heating mode winter r xx external temperature SUMMER Can be displayed if parameter Sensor 1 F fixed point regulation F fixed point regulation C Climate control I tracking adjustment WINTER ...

Page 11: ... E I HEATING h FIXED POINT CLIMATE CONTROL COOLING c FIXED POINT TRACKING ON output activated contact closed OFF output not activated contact open To access the menu when the display shows the outlet temperature to the radiant system press the B and C buttons simultaneously The display will show the E l indication Scroll the main menu with the A and B buttons Press the C button to enter the sub me...

Page 12: ...aneously The display will show the h c flashing notice Press the A key to enter the heating programming menu The menu shows different parameters depending on the type of adjustment selected Scroll the main menu with the A and B buttons Press the C button to enter the sub menu tl h1 h2 Where XX C indicates the heating set point temperature Press A or B to set the value Press C to save the value and...

Page 13: ...The display will show the h c flashing notice Press key B to enter the cooling and humidity pro gramming menu The menu shows different parameters depending on the type of adjustment selected Scroll the main menu with the A and B buttons Press the C button to enter the sub menu tE SenS Where XX C indicates the cooling set point temperature Press A or B to set the value Press C to save the value and...

Page 14: ...lue and exit the sub menu The adjustment range is from 1 0 sec to 10 0 sec default 3 0 sec Where XX sec indicates the delay time of the adjustment function from the room thermostat inlet During this time the relay output is activated closure of the M3 contact Press A or B to set the value Press C to save the value and exit the sub menu The adjustment range is from 0 sec to 100 sec default 30 sec W...

Page 15: ...by parameter P4 The motorised valve is forced on the return from the radiant system and the pump has stopped When the temperature is within the normal operating range the alarm will disappear automatically ALARM FUNCTION alarms only expected in fixed point cooling mode with relative humidity sensor and ambient temperature connected Sens parameter 1 SOTWARE RESET With the reset operation all softwa...

Page 16: ...midity sensor ELECTRICAL CONNECTIONS TO THE ACTUATOR POWER UNIT 24V DC code AL24VDC MODBUS INTERFACE USB code USBMOD DIN RAIL INSTALLATION V in 230V 50Hz V out 24V DC I out 500 mA P out 12W TECHNICAL DATA USB 2 0 to RS485 converter Backward compatible with USB 1 1 Connection via screw terminals Baud rate supported 75 bps 115200 bps up to 6 Mbps Low power consumption no external power supply requir...

Page 17: ... COMPARATO reserves the right to replace the Product with an identical one if the product is out of production it will be replaced with one with identical specifications provided that according to the unquestionable opinion of COMPARATO nello S r l the repair is not economically excusable Interventions and or repairs and or spare parts will not be covered by this Warranty if it turns out that they...

Page 18: ...DIAMIX PR COMPAMIX PR 18 COMPARA TO NELLO SRL comparato com ...

Page 19: ...DIAMIX PR COMPAMIX PR 19 COMPARA TO NELLO SRL comparato com ...

Page 20: ......

Reviews: