Fault Code  

 

Item 

Code 

Description  

E1 

Wrong Polarity or reverse connection from power input 

E2 

Low voltage protection, less than 11V 

E3 

High voltage protection, more than 18V 

P1 

No liquid temp signal from sensor   

 

Trouble shoot  

 

Item 

Problem Description  

Root Cause  

Trouble Shoot  

No Cooling Performance  

Compressor locked, 
Overheat protection, 

Low Voltage 

Check the compressor drive, 
yellow light means normal, red 

light means abnormal. 

No liquid circulation 

Check if cooling garment be 

connected, check if pump be 
turned on 

Power connection  

Check if power connection loose 

or not. 

Less cooling capacity 

Less heat exchange rate 

for evaporator  

Check if circulation water inside 

reservoir is enough or not? 

Lack of refrigerant 

Check if hot air out from 

condenser air outlet  

Low compressor speed  

Check compressor speed setting 

Low voltage 

Check unit input voltage  

No pumping 

Pump ON/OFF 

Check if pump be turned on 

Quick fitting connection  

Check quick fitting connection 

loose or not 

Pump blocked 

Check if pump be blocked 

Remote controller can’t 

operate 

Connection loose 

Check if the connection loose or 

not 

Controller LED vague or 
twinkle 

Check the unit input voltage  

5  Temp sensor 

No feedback, P1 on the 

panel 

Check if the connection loose or 

not 

 

 
 
 

Summary of Contents for COMP-MLCS-12200

Page 1: ...Compcooler keep your body cool and comfortable in harsh conditions 1 Motorcycle Rider Liquid Chiller System Model COMP MLCS 12200 Rev A Operation Manual ...

Page 2: ...oyees at Compcooler s state of the art manufacturing facility have been producing liquid heating cooling systems over 15 years Quality system ISO9001 and AS9100 registered facility Certifications for major items CE FCC UL PSE CB FDA Product Categories 1 ICE Water Circulation Systems 2 Micro Refrigeration Chiller Units 3 Liquid Heating Systems 4 Liquid Cooling Heating Garment and Pad 5 Customized C...

Page 3: ...trol 5 to 30 23 to 86 accuracy 1 2 once circulation liquid reaches to set point temperature system intellectually control the cooling capacity to that temperature User may pre cool the unit and get the coldest liquid as he needs iceless cooling unit maintain free Components List Item Part number Description Quantity 1 COMP HLCU Handcarry Liquid Chiller Cooling Unit 1 DC Connection Power Cord EC5 1...

Page 4: ...nsumption W 200 Refrigerant Type R134a Temp Control 5 to 30 23 86 Coolant Anti freeze liquid Yes Rotary Compressor Samsung Qty PC 1 Voltage V DC 12 Discharge CC 1 9 Speed RPM 2000 6500 Fan Qty PC 2 Voltage V DC 12 Air Flow CFM 30 Pump Voltage V DC 12 Water flow L Min 1 Lift M 2 Power Connector Type DC EC5 Operation Ambient Max 10 to 60 Storage Temp 20 to 70 Noise Max dBA 58 Color White or Black Di...

Page 5: ...ay be changed for different ambient Chiller Unit Performance Curves Operation ambient for chiller unit is 10 to 60 Cooling capacity could be difference based on ambient and liquid temp setting 0 50 100 150 200 250 300 5 10 15 20 25 Cooling Capacity W Coolant Temperature Performance Curves Ambient 20 Ambient 30 Ambient 40 0 2 4 6 8 10 12 14 16 18 0 20 40 60 80 100 Current of Chiller DC 12V Operatio...

Page 6: ...ction Preparation Chiller Unit Installation Unit could be fixed on the rear or side of motorcycle make sure it is a well ventilated area no blocks for fresh air inlet and outlet Power Connection Vehicle Power connection One DC power cord EC5 was provided with chiller user may connect it with Vehicle power 12 16V ...

Page 7: ...ension hose and replace the new fittings to compatible with other cooling garment Circulation Liquid User needs to fill circulation liquid by twice The first time remove the filler cap from top side add liquid to full by funnel connect the cooling garment turn on the pump and circulates the liquid from reservoir to cooling garment The second time keep running and allow the liquid cooling garment f...

Page 8: ...nnection connect with power EC5 connection light the controller The cooling unit will be in standby mode 3 Start cooling user may press ON OFF to start chiller liquid temperature will go down to set point in minutes pump is not working at this time 4 Temp setting user may press up and down to set up the temp for circulation liquid as need 5 Start circulation User may press the pump to start or sto...

Page 9: ...ed operator If cooling capacity was decreased because of lack of refrigerant user may vacuum the unit and recharge 150g R134a refrigerant Liquid Heating Cooling garment Prefer to clean by hand wash then hang dry Machine wash by Laundry bag wash liquid heating and cooling vest using a front loading wash machine with cold water on a gentle delicate cycle Note DO NOT BLEACH NO IRON NO DRYER TUMBLE DR...

Page 10: ...nnected check if pump be turned on Power connection Check if power connection loose or not 2 Less cooling capacity Less heat exchange rate for evaporator Check if circulation water inside reservoir is enough or not Lack of refrigerant Check if hot air out from condenser air outlet Low compressor speed Check compressor speed setting Low voltage Check unit input voltage 3 No pumping Pump ON OFF Chec...

Page 11: ...se Safety It is important to become thoroughly familiar with the manual and operating characteristics of the unit It is the owner s responsibility to assure proper operator training installation operation and maintenance of the unit Observe all warning can result in injury to the operator and severe mechanical damage to the unit Warranty Compcooler Warrants to the original Purchaser that products ...

Reviews: