- 8 -
circuit). If there are no such zones, then in order to prevent the heating system
from an event in which all heating circuits are closed but a pump is switched on,
the zone controller has two types of delay function.
5.1 Turn on delay
If this function is activated and the outputs of the thermostats are switched off,
then in order to open the valves of the given heating circuit before starting the
pump(s), the zone controller
NO
-
COM
and
Z1-4
output, and depending on the
zone the
Z1-2
or
Z3-4
output switches on only after a delay of 4 minutes from the
1st switch-on signal of the thermostats, while 230 V appears immediately at the
output for that zone (eg.
Z2
). The delay is especially recommended if the zone
valves are opened/closed by slow-acting electrothermal actuators, because their
opening/closing time is approx. 4 min. If at least 1 zone is already switched on,
then the Turn on delay function will not be activated when additional thermostats
switch on.
The active state of the Turn on delay function is indicated by the blue LED flashing
with 3-second intervals.
If the “
A
/
M
” button is pressed while the Turn on delay is active (blue LED flashes
with 3-second intervals), the LED stops flashing and indicates the current
operating mode (Automatic/Manual). Then the working mode can be changed
by pressing the “
A
/
M
” button again. After 10 seconds, the blue LED continues to
flash with 3-second intervals until the delay stops.
5.2 Turn off delay
If this function is activated and some thermostat outputs of zone controller are
switched on, then in order for the valves belonging to the given zone to be
open during the recirculation of the pump(s), the 230 V AC voltage disappears
from the zone output of the given zone (eg
Z2
), output
Z1-4
and, depending
on the switched zone, output
Z1-2
or
Z3-4
only after a delay of 6 minutes from
the switch-off signal of the last thermostat, while the
NO
-
COM
output switches
off immediately. The delay is especially recommended if the zone valves are
opened/closed by quick-acting motorized actuators, as their opening/closing
time is only a few seconds. Activating the function in this case ensures that the
heating circuits are open during the circulation of the pump and thus protects
the pump from overload. This function is only activated when the last thermostat
sends the switch-off signal to the zone controller.
The active state of the Turn off delay function is indicated by the 3-second
interval flashing of the red LED of the last zone switched off.