Power supply
230V AC
Max. load
16 (4) A
Output signal
terminals 1/C/2 (NO/COM/NC)
Temperature adjustment range
30 – 90 °C
Dimension [mm]
105 x 50 x 45
AT10F: length of the capillary:
1200,
Ø
of the capillary: 7
Technical informations
Montage
Changing temperature setpoint
AT10:
For installation, press the thermostat firmly to the heat pipe and
fix it with the supplied elastic band so that the thermostat is in direct
contact with the pipe (remove any insulation at the installation spot
before fixing the sensor). Excess elastic band can be trimmed.
AT10F:
Fix the thermostat to a flat surface using screws. Then place the
measuring element (capillary) in the measuring sleeve, e.g. located in
the hot water tank.
To set the temperature, pull the knob towards you to release it. Then
turn the knob to the position which indicates the required temperature.
To keep this setting, press the knob lightly in the inward direction until
a click is heard.