Sentinel 150P installation, operation & maintenance 

ci0050   p4/8   issue 5   2014-08-26 

 

Dimensions and Assembly 

 

 

 

CAUTION:

 Sentinel 150P chargers should be handled by the circuit board cover. Care should be taken not to 

handle static sensitive components through exposed circuit boards and terminals. 

 

 

SNTL150P 

 

 

 

12V models 

24V models 

Overall: 

108.6 mm / 4.28 in. 

135 mm / 5.31 in. 

45 mm / 1.77 in. 

55 mm / 2.17 in. 

Fixing holes: 

99 mm / 3.90 in. 

Ø 5.65 mm / 0.22 in. 

Weight: 

 

0.65 kg / 1.43 lb. 

0.75 kg / 1.65 lb. 

 

  These chargers are designed for mounting in a vertical plane inside an enclosed control panel or housing.  

Mounting orientation should be as shown above, with electrical connection terminals uppermost. 

  For safe heat dissipation, mount Sentinel in the orientation shown, with a minimum air-gap clearance of 40mm/1.5 in. 

above/below and 25mm/1 in. at the sides. Consideration must be given to ventilation for proper heat dissipation. 

 

For surface mounting, use the 2 centre fixing holes (Ø 5.65mm/0.22 in.). Ensure that the mounting studs/bolts/nuts/screws 
adequately support the charger, and are tightened sufficiently to not to become loose during normal use, e.g. due to 
engine/equipment vibration..

 

Electrical Connection & Configuration 

 

DANGER !

HIGH VOLTS

 

WARNING: DANGER OF INJURY OR DEATH. During normal operation, Sentinel is 
connected to high voltage AC circuits. Before connection, disconnection or handling of 
these chargers, ensure isolation of all AC power supplies. Connection or disconnection with 
live wiring can also cause hazardous sparking and component damage. 

Connection terminals (general) 

The Sentinel 150P uses a pair of two-part connectors with 
removable screw terminal blocks: 

 

CN1:

 a 7-way block for connection of the DC charge 

output, temperature compensation remote sensor, relay 
output and configurable input. Use a 5 mm/0.2 in. flat-
head screwdriver to tighten/loosen the terminals. For the 
DC output, use 2.5mm/13AWG or larger connecting 
wire.  

 

CN3:

 a 3-way block for connection of the mains AC power 

supply live, neutral and ground. Use a 5mm/0.2in flat-
head screwdriver to tighten/loosen the terminals.  
For all AC supply/ground wiring, use 1mm/17AWG or 
larger wire conductors rated for temperature 90°C/194°F. 
For external fuse details, see the 

AC Input (power 

supply)

 section following.  

3 LEDs (coloured blue, green, red) provide indication of AC 
supply, DC charge output and fault status. 

For all models, wire connections for the DC charge output 
(connector block CN1) and AC input supply (CN3) must be 
physically separated, e.g. separate wire harnesses, 
separately routed through the panels/ducting.

 

 

DC Charge Output 

 

Before DC connection or disconnection:- 

  Ensure AC supply input is isolated. 

Disconnecting the batteries while the  
AC supply is live can result in sparking at 
the battery terminals, ignition of battery 
gasses and serious personal injury.

 

  Check that the charger model and output 

ratings are compatible with battery type & 
voltage (see table below).

 Incompatibility 

may result in damage to the charger, 
batteries and serious personal injury.

 

Connect the Sentinel DC charge output to the battery terminals, 
observing the warnings above and the correct  
DC polarity:  

CN1 
pin 

Function 


+ DC charge output  
– DC charge output 

All SNTL150P models include an electronic, self-resetting DC 
output fuse for protection of reverse polarity and short-circuit 
faults. In the event of such faults, remove the cause of fault: the 
charger will then attempt to automatically reset its fuse and re-
initialise the output. If the fuse fails to reset, contact your supplier 
for further advice. 

 

 

Summary of Contents for Sentinel 150P series

Page 1: ...change our specifications and designs at any time Computronic Controls products and the Computronic Controls logo are registered and or common law trademarks of Enovation Controls LLC This document i...

Page 2: ...and damage to property ix DANGER OF EXPLOSION NEVER CHARGE A FROZEN BATTERY PRIOR TO INSTALLATION COMMISSIONING Clean battery terminals Be careful to keep corrosion from coming into contact with eyes...

Page 3: ...cover for surface mounting in an enclosed panel Electrical connection of the AC supply battery and control circuits is via screw terminal blocks Model options Model codes with suffix A SNTL150P CDA ad...

Page 4: ...y block for connection of the DC charge output temperature compensation remote sensor relay output and configurable input Use a 5 mm 0 2 in flat head screwdriver to tighten loosen the terminals For th...

Page 5: ...uffix A models SNTL150P CDA additionally include one relay output and one digital switch input The functions of input and output can be configured using the SNTL150P PCSUITE software tool Output The s...

Page 6: ...AWG or larger wire conductors rated for temperature 90 C 194 F The AC live wiring must incorporate fuse ratings types as indicated on the charger labelling Sentinel PC connection SNTL150P PCCON confi...

Page 7: ...ease in output voltage It may be initiated automatically on battery low voltage programmable level factory default 12 0V 24 0V automatically on expiry of a time interval since the last AutoBoost progr...

Page 8: ...Sentinel 150P installation operation maintenance ci0050 p8 8 issue 5 2014 08 26 Fault Finding Warranty and Maintenance Troubleshooting Flowchart...

Reviews: