26. Check the operation of all control and safety devices in the burner control circuits.
In addition, ensure that the burner operates correctly. Make a note of all control settings.
27. The low fire setting of the burner should be made in line with the process requirements
whilst still maintaining a steady flame signal.
NOTE;-
Once correctly commissioned the burner settings should only be altered by suitably
qualified personnel, and only when changes to the process requirements deem it
necessary. At no point should the settings of any safety device be altered to overcome
changes in process conditions without the burner again being fully commissioned in line
with those process conditions.
Initial Light Up (Commissioning)
Comtherm Ltd
Installation & Maintenance Manual
Page 09
Burners, Heaters & Combustions Systems