Burners can be supplied to suit almost all types of electrical power supply; including all
common industrial three phase (50 or 60Hz) power supplies and with 110/120v or
220/240v control circuits.
Burners to suit other electrical supply voltages can be supplied specially to suit specific
application requirements.
All wiring on the burner should comply with the requirements of the local electrical codes of
practice.
All conduits should be kept clear of heat zones.
Local means of electrical isolation should be installed close to the burner.
Ensure that the electrical voltage does not vary from the specified by more than 6%.
High temperature wire (tri-rated or better) should be used for all electrical connections.
The electrical connections to the burner shown on diagram M5 should be strictly adhered to.
Gas pipe work should not be used as an electrical earth.
Installation (Continued)
Comtherm Ltd
Installation & Maintenance Manual
Page 05
.
Burners, Heaters & Combustions Systems