Table 3 – ESER Series Single-Circuit Remote Air-Cooled Condenser Chiller General Data (60 Hz)
ESER-
ESER-
ESER-
ESER-
ESER-
ESER-
ESER-
ESER-
ESER-
010S
015S
020S
025S
030S
040S
050S
060S
080S
General
Cooling Capacity tons
1
10
14.9
20.4
25.2
30.1
38.9
48.9
63.6
78.7
Set Point Range °F
20 to 80
20 to 80
20 to 80
20 to 80
20 to 80
20 to 80
20 to 80
20 to 80
20 to 80
Process In/Out (in.)-
Standard
1½
1½
2
2
2½
2½
3
3
4
Process In/Out (in.)-
High Flow
2
2½
2½
3
3
4
4
4
N/A
Refrigerant Discharge Line inch
⅞
1
⅛
1
⅛
1
⅜
1
⅜
1
⅝
1
⅝
1
⅝
2
⅛
Refrigerant Liquid Line inch
⅝
⅞
⅞
1
⅛
1
⅛
1
⅛
1
⅛
1
⅜
1
⅝
Refrigerant Charge (lbs of
R410A)
Varies based on refrigerant system piping
Min
Unloaded
Capacity ton
5.0
7.4
10.0
12.5
14.8
19.1
23.6
30.9
38.5
with HGBP Option ton
2.5
3.7
5.0
6.2
7.4
9.6
11.8
15.5
19.3
Dimensions, Weights, Amps (Chiller Only)
A - Length inches {mm}
68 {1727}
68 {1727}
68 {1727}
68 {1727}
72 {1829}
102 {2591}
102 {2591}
102 {2591}
105 {2667}
B - Width inches {mm}
24 {610}
24 {610}
24 {610}
24 {610}
24 {610}
24 {610}
30 {762}
30 {762}
30 {762}
C- Height inches {mm}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
69 {1753}
Ship Weight lbs {kg}
1200 {544} 1300 {590}
1400 {635}
1500 {680}
1600 {726}
1800 {816}
2000 {907}
2200 {998} 2400 {1089}
Operating Weight lbs {kg}
1300 {590} 1400 {635}
1500 {680}
1600 {726}
1700 {771}
1900 {862}
2100 {953} 2300 {1043} 2500 {1134}
MCA @ 460/3/60 amps
2
22
34
42
53
62
71
86
124
165
Dimensions, Weights, Amps (Chiller with Standard Flow Reservoir Option , 10°F ∆T Process, 10°F ∆T Chiller)
Reservoir Capacity gal {l}
275 {1041} 275 {1041}
275 {1041}
275 {1041}
275 {1041}
275 {1041}
275 {1041}
450 {1703}
450 {1703}
Pump Models (Process/Chiller)
5D/1.5A
5D/1.5A
5D/1.5A
5D/1.5A
7.5D/2A
10D/2A
10D/3A
10D/3A
15D/3A
Process Connection Size inch
1½
1½
2
2
2½
2½
3
3
4
D - Length inches {mm}
84 {2134}
84 {2134}
84 {2134}
96 {2438}
96 {2438}
96 {2438}
96 {2438}
108 {2743}
108 {2743}
E - Width inches {mm}
64 {1626}
64 {1626}
64 {1626}
76 {1930}
76 {1930}
92 {2337}
92 {2337}
96 {2438}
98 {2489}
F - Height inches {mm}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
75 {1905}
Ship Weight lbs {kg}
2600 {1179} 2700 {1225} 2900 {1315} 3200 {1451} 3900 {1769}
4100 {1860} 4700 {2132} 5100 {2313} 5400 {2449}
Operating Weight lbs {kg}
4900 {2223} 5000 {2268} 5100 {2313} 5500 {2495} 6200 {2812} 6400 {2903} 7000 {3175} 7400 {3357} 7800 {3538}
MCA @ 460/3/60 amps
2
32
43
50
62
75
86
104
141
188
Dimensions,
Weights, Amps (Chiller with High Flow Reservoir Option 1, 5°F ∆T Process, 10°F ∆T Chiller)
Reservoir Capacity gal {l}
400 {1514} 400 {1514}
400 {1514}
400 {1514}
400 {1514}
400 {1514}
400 {1514}
650 {2460}
650 {2460}
Pump Models (Process/Chiller)
5D/1.5A
7.5D/1.5A
10D/1.5A
10D/1.5A
10D/2A
15D/2A
15D/3A
20D/3A
25D/3A
Process Connection Size inch
2
2½
2½
3
3
4
4
4
6
D - Length inches {mm}
84 {2134}
84 {2134}
84 {2134}
96 {2438}
96 {2438}
96 {2438}
96 {2438}
108 {2743}
108 {2743}
E - Width inches {mm}
64 {1626}
64 {1626}
64 {1626}
76 {1930}
92 {2337}
92 {2337}
92 {2337}
96 {2438}
98 {2489}
F - Height inches {mm}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
76 {1930}
Ship Weight lbs {kg}
2800 {1270} 2900 {1315} 3100 {1406} 3400 {1542} 4100 {1860} 4300 {1950} 4900 {2223} 5350 {2427} 5650 {2563}
Operating Weight lbs {kg}
5950 {2699} 6050 {2744} 6150 {2790} 6550 {2971} 7250 {3289} 7450 {3379} 8050 {3651} 9050 {4105} 9450 {4286}
MCA @ 460/3/60 amps
2
32
46
57
68
78
91
109
153
201
1
Cooling capacity when cooling water with 50°F {10°C} set point, 60°F {16°C} return, 95°F {35°C} condenser air, R-410A
refrigerant.
2
MCA is Minimum Circuit Amps (for wire sizing).