39
Table 15 – ESEW & ESER Single-Circuit Chiller with High Flow Pump Set 1 Electrical Data (60 Hz)
Model
Main Power
(3-phase, 60 Hz)
Compressors
Pumps
Chiller
Rated
Allowable
Qty
RLA
1
LRA
2
Process
Pump
Chiller Pump
MCA
4
MOPD
5
Min
Max
(ea)
(ea)
Qty
FLA
3
Qty
FLA
3
ESEW-010S
& ESER-010S
208
187
253
2
19.0
123
1
16.6
1
5.3
65
80
230
187
253
2
19.0
123
1
15.0
1
4.8
63
80
460
414
508
2
9.7
62
1
7.5
1
2.4
32
40
575
518
632
2
7.4
50
1
6.0
1
1.9
25
30
ESEW-015S
& ESER-015S
208
187
253
2
29.5
195
1
24.3
1
5.3
96
125
230
187
253
2
29.5
195
1
22.0
1
4.8
93
110
460
414
508
2
14.7
95
1
11.0
1
2.4
46
60
575
518
632
2
12.2
80
1
8.8
1
1.9
38
50
ESEW-020S
& ESER-020S
208
187
253
2
33.3
239
1
31.0
1
5.3
111
125
230
187
253
2
33.3
239
1
28.0
1
4.8
108
125
460
414
508
2
17.9
125
1
14.0
1
2.4
57
70
575
518
632
2
12.8
80
1
11.2
1
1.9
42
50
ESEW-025S
& ESER-025S
208
187
253
2
51.3
300
1
31.0
1
5.3
152
200
230
187
253
2
51.3
300
1
28.0
1
4.8
148
200
460
414
508
2
23.1
150
1
14.0
1
2.4
68
90
575
518
632
2
19.9
109
1
11.2
1
1.9
58
70
ESEW-030S
& ESER-030S
208
187
253
2
55.8
340
1
31.0
1
6.6
163
200
230
187
253
2
55.8
340
1
28.0
1
6.0
160
200
460
414
508
2
26.9
173
1
14.0
1
3.0
78
100
575
518
632
2
23.7
132
1
11.2
1
2.4
67
90
ESEW-040S
& ESER-040S
208
187
253
2
72.4
538
1
42.0
1
6.6
212
250
230
187
253
2
72.4
538
1
38.0
1
6.0
207
250
460
414
508
2
30.8
229
1
19.0
1
3.0
91
110
575
518
632
2
25.0
180
1
15.2
1
2.4
74
90
ESEW-050S
& ESER-050S
208
187
253
2
85.3
605
1
42.0
1
10.0
244
300
230
187
253
2
85.3
605
1
38.0
1
9.0
239
300
460
414
508
2
37.8
320
1
19.0
1
4.5
109
125
575
518
632
2
34.6
250
1
15.2
1
3.6
97
125
ESEW-060S
& ESER-060S
208
187
253
2
109.6
599
1
57.5
1
10.0
314
400
230
187
253
2
109.6
599
1
52.0
1
9.0
308
400
460
414
508
2
54.5
310
1
26.0
1
4.5
153
200
575
518
632
2
49.4
239
1
20.8
1
3.6
136
175
ESEW-080S
& ESER-080S
208
187
253
2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
230
187
253
2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
460
414
508
2
73.0
368
1
32.0
1
4.5
201
250
575
518
632
2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1
RLA is Rated Load Amps.
2
LRA is Locked Rotor Amps.
3
FLA is Full Load Amps.
4
MCA is Minimum Circuit Amps (for wire sizing), complies with NEC, Section 430-24.
5
MOPD is Maximum Over-current Protection Device, complies with NEC, Section 430-53.