Alarm Setup
Alarm set points and timers are modifiable on the Alarm Setup Screen (Figure 28).
Figure 28 – Alarm Setup
Alarm Glycol
If the Chiller Setpoint goes below 45°F {7°C}, the Glycol Warning Screen will appear as in Figure 29. The amount of
antifreeze will vary depending on the actual desired operating conditions and should be enough to provide freeze
protection to temperatures 15°F {-9°C} colder than the coldest temperature anticipated. Use only antifreeze
solutions designed for heat exchanger duty. Do not use automotive antifreeze due to the potential for fouling that
can occur once its relatively short-lived inhibitors break down. Verify the proper Glycol solution is used and
“Accept” the Warning.
Figure 29 – Alarm Setup