Menu 1 – EXV2 Hot Gas Bypass Setup
EXV2 Hot Gas Bypass Setup Screen (Optional)
Figure 39 – EXV2 Hot Gas Bypass Screen
Table 26 – EXV2 Setup Parameters
Menu Item
Description
Default
Value
Mode Selection
OFF: The valve will always be closed (zero output)
AUTO-LAST COMP ONLY: The valve will only respond relative to the demand PID
when operating with the last compressor running.
AUTO-ALWAYS ON: The valve will always respond relative to the demand PID
regardless of how many compressors are running.
MANUAL MODE: The manual mode value percent will be the output to the valve.
AUTO
ALWAYS ON
Minimum Position
The minimum percent the valve will go to.
0%
Maximum Position
The maximum percent the valve will go to.
100%
Kp
Proportional PID value
1000
Ti
Integral PID value
500
Td
Derivative PID value
0