Compressor Staging Local Screen
The Compressor Staging Local Screen (Figure 43) depicts the stage order of the local chiller. The stage order will
auto calculate based off of the hours entered in the auto stage hours parameter. The intent is to run the
compressors with the least amount of hours first to help equalize the run hours of all the compressors.
Figure 43 – Compressor Staging Local Screen
Table 30 – Compressor Staging Local Parameters
Menu Item
Description
Default
Value
Manual Trigger
Manual Trigger will immediately recalculate the stage order instead of waiting for
the automatic trigger to occur.
None
Manual OFF/ON
Allows the ability to manually activate a compressor for testing purposes
OFF
Stage Mode
Automatic: calculates the stage order by the AUTO STAGE HOURS parameter
Manual: Manually enter the stage order
AUTOMATIC
Auto Stage Hours
The number of run hours before recalculating the stage order
24 HOURS
Minutes Until Auto
stage
Minutes remaining until the stage calculation occurs
None
Compressors requested
Local
The number of compressor requested by the master control from this chiller
None