Communication table
4
Communication table
4.1
Data points
The following table shows which object functions can be linked with the KNX home automation via the
group addresses of the "MN option KNX.KNXPROJ":
Data point
Object function
Description
Range
Type
1
Name Area 1
Name of zone 1
DPT 16
2
Name Area 2
Name of zone 2
DPT 16
…
Name Area [n]
Name of zone [n]
DPT 16
20
Name Area 20
Name of zone 20
DPT 16
32
System Name String
Name of the MN Condair
DPT 16
33
Humidity Area 1
Actual humidity value zone 1
0 - 100%
DPT 09
34
Humidity Area 2
Actual humidity value zone 2
0 - 100%
DPT 09
…
Humidity Area [n]
Actual humidity value zone [n]
0 - 100%
DPT 09
52
Humidity Area 20
Actual humidity value zone 20
0 - 100%
DPT 09
53
Temperature Area 1
Actual temperature value zone 1
100 +200°C
DPT 09
54
Temperature Area 2
Actual temperature value zone 2
100 +200°C
DPT 09
…
Temperature Area [n]
Actual temperature value zone [n]
100 +200°C
DPT 09
72
Temperature Area 20
Actual temperature value zone 20
100 +200°C
DPT 09
73
Setpoint Off Area 1
Humidification level 0 "Humidifica-
tion Off" of zone 1
0 = inactive
1 = active
DPT 01
74
Setpoint Off Area 2
Humidification level 0 "Humidifica-
tion Off" of zone 2
0 = inactive
1 = active
DPT 01
…
Setpoint Off Area [n]
Humidification level 0 "Humidifica-
tion Off" of zone [n]
0 = inactive
1 = active
DPT 01
92
Setpoint Off Area 20
Humidification level 0 "Humidifica-
tion Off" of zone 20
0 = inactive
1 = active
DPT 01
93
Setpoint Low Area 1
Humidification level 1 "Humidifica-
tion Low" of zone 1
0 = inactive
1 = active
DPT 01
94
Setpoint Low Area 2
Humidification level 1 "Humidifica-
tion Low" of zone 2
0 = inactive
1 = active
DPT 01
…
Setpoint Low Area [n]
Humidification level 1 "Humidifica-
tion Low" of zone [n]
0 = inactive
1 = active
DPT 01
112
Setpoint Low Area 20
Humidification level 1 "Humidifica-
tion Low" of zone 20
0 = inactive
1 = active
DPT 01
113
Setpoint Norm Area 1
Humidification level 2 "Humidifica-
tion Mid" of zone 1
0 = inactive
1 = active
DPT 01
114
Setpoint Norm Area 2
Humidification level 2 "Humidifica-
tion Mid" of zone 2
0 = inactive
1 = active
DPT 01
…
Setpoint Norm Area [n]
Humidification level 2 "Humidifica-
tion Mid" of zone [n]
0 = inactive
1 = active
DPT 01
132
Setpoint Norm Area 20
Humidification level 2 "Humidifica-
tion Mid" of zone 20
0 = inactive
1 = active
DPT 01
133
Setpoint High Area 1
Humidification level 3 "Humidifica-
tion High" of zone 1
0 = inactive
1 = active
DPT 01
134
Setpoint High Area 2
Humidification level 3 "Humidifica-
tion High" of zone 2
0 = inactive
1 = active
DPT 01