3
6
Operation
Proceed as follows when putting the unit into operation:
1.
Examine the steam generator and installation for possible damage
.
WARNING!
Damaged devices or devices with damaged installation may present danger to
human life or cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation must not
be operated.
2. Check whether the front panel is mounted and fixed with the two screws.
3. Open the
filter valve
(or the shut-off valve, respectively) in the water supply line.
.
Switch on the service switches
for mains supplies (heating and control voltage).
.
Actuate the unit switch
of the steam generator.
Switch lights up
.
6.1
Commissioning
STARTUP:
CP3 STEAMBATH
INIT MODULE
XXXXXXXXXXXXXXXXXXXX
Menu
Set
The steam generator carries out a
system test
, during which all the
LEDs light up and the opposite display is shown.
If a failure occurs on the system test, a corresponding error message
is shown in the display.
After the system test the
operating display
is shown.
Note: The contents of the operating display and the setting of the keys
depend on the actual operating status and on the configuration of the
Condair CP3 D and can differ from the opposite display.
Depending on the selected operating mode of the Condair CP3 D,
the steam generator must manually be started via the Start/Stop
button of the display and control unit or via an external Start/Stop
button or the operation runs time-controlled via the day timer or the
week timer. As soon as the steam generator is started, the heating
current is switched on.
The inlet valve opens (slight delay) and the
steam cylinder fills with water. As soon as the submerged electrodes
heat the water up the green LED lights up and after a few minutes
(approx. –10 minutes, depending on the conductivity of the water)
steam is produced
and the steam bath cabin is heated up. As soon
as the set temperature in the steam bath cabin is achieved, the light
is switched on and the bath phase starts. During the bath phase the
fragrance pump (if available) is controlled in accordance with the se-
lected operating mode and the fan (or the flap actuator) is controlled
in accordance with the set temperature and the actual temperature
in the steam bath cabin.
Note: If the Condair CP3 D is operated with water of low conductivity it may happen that the
maximum steam capacity is not reached in the first few hours of operation. This is normal. As
soon as the conductivity has reached a sufficient level (due to the vaporisation process) the steam
generator will reach the maximum steam capacity.
Steam Bath :Standby
CP3 D45 400V3
Temperature :34°C
Setpoint :48°C
05.05.2008 12.00.00
Start
Menu
Light
Steam Bath :Heating
CP3 D45 400V3
Temperature :34°C
Setpoint :48°C
05.05.2008 12.00.00
Stop
Menu
Light