3
6.2.3
Inspections during operation
During operation the Condair CP3 D and the humidification system have to be inspected weekly. On
this occasion check the following:
• the water and steam installation for any leakage.
• the steam generator and the other system components for correct fixing and any damage.
• the electric installation for any damage.
If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged components
take the Condair CP3 D out of operation as described in chapter .3. Then, contact your Condair
representative.
6.2.4
Carrying out manual draining
Proceed as follows to drain the unit manually:
Manual Drain
Modul A
Press START or STOP
Esc
Set
Start
6.3
Taking the unit out of operation
In order to take the steam generator out of operation, perform the following steps:
1. If the unit has to be switched off because of a malfunction, please note the error code of the
actual error message shown in the display.
2. Close the shut-off valve in the water supply line
3. Start manual draining (see chapter .2.) and wait until the steam cylinder is empty.
.
Actuate the unit switch
.
Disconnect steam generator from the mains
: Switch off all service switches to mains supplies
(heating and control voltage) and secure switches in “off” position against accidentally being
switched on, or clearly mark the switches.
WARNING!
If steam was produced just before the unit is taken out of operation, wait be-
fore opening the unit and let the steam cylinder cool down to prevent danger
of burning.
1.
Briefly press the drain key
. The drain dialogue appears in the
display.
2. Press the
<Start>
key. The heating voltage is interrupted and the
drain pump starts. The
yellow LED flashes
.
To stop the drain cycle press the
<Stop>
key.
Note: By pressing the
<Esc>
key the unit returns to the indication
level. A drain cycle in progress will be stopped automatically.