Temp.Sensor
:
With the settings in the submenu “Temp.Sensor” you can determine the
signal source as well as the type and the signal sizes of the used sen-
sor.
–
SignalSource
:
Setting the signal source.
Factory setting:
Analog
Options:
Analog, Modbus
–
Type
:
Setting the type of the sensor in use (this menu
item is available only if signal source is set to
“Analog”).
Factory setting:
KTY
Options:
KTY (included in the delivery), 0...10V
–
Nom. Value
:
Set the nominal value of the KTY sensor in Ohm.
Note: this setting is available only if sensor type “KTY” is selected.
Factory setting:
2020
Setting range:
1900...2100
–
0V-Temp.
:
Setting the temperature value in °C which equals
to 0 V for a 0-10V temperature sensor.
Note: this setting is available only if sensor type “0-10V” is selected.
Factory setting:
0°C
Setting range:
-50 ... +20°C
–
100V-Temp.
:
Setting the temperature value in °C which equals
to 10 V for a 0-10V temperature sensor.
Note: this setting is available only if sensor type “0-10V” is selected
Factory setting:
100°C
Setting range:
+80 ... +200 °C
–
Temp.Control
:
Setting the type of temperature control.
Factory setting:
Int.(P)
Options:
Int. (P)
(Internal P controller)
Int. (PI)
(Internal PI controller)
–
P-Band
:
Setting the proportional range in °C for the internal P/PI controller.
Note: This setting is available only if the internal P or PI controller is acti-
vated.
Factory setting:
4°C
Setting range:
1...60°C
–
Integr.-Time
:
Setting the integral time in minutes for the internal PI controller.
Note: This setting is available only if the internal PI controller is activated.
Factory setting:
2 minutes
Setting range:
1...60 minutes
Temp.Sensor
SignalSource:Modbus
Esc
Set
Temp.Sensor
Type :KTY
Nom. Value :2020
Signalsource:Analog
Esc
Set
Temp.Sensor
Type :0-10V
0V-Temp. :0°C
10V-Temp. :100°C
SignalSource:Analog
Esc
Set