6.6.4.7 Setting the capacity limitation
Select “
Power Limit
” in the settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired power limit in %
of the maximum capacity.
6.6.4.8 Activating/Deactivating fault current relay operation
Select “
GFCI-Mode
” in the settings menu, then press the
<Set>
key.
In the upcoming modification dialogue select whether or not the Condair
CP3 D is connected to a fault current relay protected mains supply.
Factory setting:
Off
Options:
On
(mains supply with fault current relay protec-
tion)
Off
(mains supply without fault current relay
protection)
6.6.4.9 Water management settings
Select “
Water Manag.
” in the settings menu, then press the
<Set>
key.
The water management settings menu appears.
Press the
< >
and
< >
keys in order to select the individual settings and
press the
<Set>
key to call up the modification dialogue for the selected
setting.
Description of the water management settings
–
Conductivity
:
Selecting the conductivity range of the supply water.
Factory setting:
>125 μS/cm
Options:
>125 μS/cm
,
<125 μS/cm
–
Drain Factor
:
Setting the drain factor
Factory setting:
1.0
Setting range:
0.5...2.0
–
StandbyDrain
:
Selecting the type of draining which takes place after a certain time (see
following setting) of
standby operation
.
Factory setting:
Full
Options:
Full
(complete draining)
Partial
(partial draining) **
Off
(draining deactivated)
** The cylinder is drained so far that the water does not touch the elec-
trodes any longer.
Settings
Cylinder :Set
Power Limit :100%
GFCI-Mode :Aus
Teit :12:00
Water Manag.:Set
Esc
Set
Settings
Power Limit :100%
GFCI-Mode :Aus
Water Manag.:Set
Cylinder :Set
Remote Test :Set
Esc
Set
Settings
GFCI-Mode :Aus
Water Manag.:Set
Remote Test :Set
Power Limit :100%
Bath Test :Set
Esc
Set
Force Delay :72h
Water Manag.
Drain Factor:1.0
StandbyDrain:Full
StandbyDelay:72h
Conductivity:>125µS
Force Drain :On
Esc
Set