16
Operation
Condair TE
5.6.4
Remote Starting and Stopping via External Signal Input (DIP Switch Settings)
Remote starting and stopping via external control signal input (external command control) is possible.
However, even with this type of operation, remote controller installation is still required.
When using both a remote controller and external control signal inputs to start and stop the humidifier,
the system utilizes second-Input priority. External control signal input types include steady-state input
and instantaneous input, with steady-state input signals used as default.
To enable external control signal input (remote starting and stopping):
1. Remove power to the humidifier. Failure to do so may prevent changes from saving.
2. Connect control wires from the external controller to terminals 4, 5, and 6 on the main humidifier
terminal block.
3. Set DIP switch 3 pin 1 ON or OFF for your configuration.
Table 5: DIP switch settings for remote starting and stopping with external control signal
Humidifier Wiring
DIP Switch Setting
Notes:
Steady-state input signal
(default setting)
6
4
5
DS3 pin 1 OFF
Working voltage 12 VDC 10 mA. Input an ON contact signal
when operating and an OFF signal when stopping.
Pressing the remote controller’s power button when the
humidifier operation is stopped will start operation, and
pressing it when the humidifier is already operating will stop
operation.
Due to the use of second-input priority, contact must be
switched from ON to OFF in order to enable forced oper
-
ation stoppage via ext. control signal input. Similarly, the
contact must be switched form OFF to ON in order to enable
forced operation start.
Instantaneous input signal
ON OFF
6
4
5
COM
DS3 pin 1 ON
Working voltage 12 VDC 10 mA. Input a contact signal with
duration at least 0.1 seconds.
Pressing the remote controller’s power button when the
humidifier operation is stopped will start operation, and
pressing it when the humidifier is already operating will stop
operation.