35
Product Specifications
Condair TE
9
Product Specifications
Model/Type
Condair Ceiling Mounted Evaporative Humidifier
Model No. and product name
Condair TE-05
Standard humidification capacity
Fan-High (60 Hz)
4.85 lb/h (2.2 kg/h)
Fan-Low (60 Hz)
2.43 lb/h (1.1kg/h)
at 73.4°F (23°C) and 40% RH. Standard humidification capacity varies depending on intake air conditions.
Rated Air Flow
Fan-High (60 Hz)
20 129 ft
3
(570 m
3
), 350 cfm
Fan-Low (60 Hz)
9 888 ft
3
(280 m
3
), 175 cfm
Operating noise
40 dBA at high fan operation (60 Hz), and 21 dBA at low fan operation) (60 Hz)
Air flow switching
Two fan speed levels: high and low, toggled via remote controller (two-position humidistat installation supported)
Rated power source
120 VAC, 60 Hz
Rated power consumption
97 W (at high fan speed with waste water drainage pump operating 60 Hz)
Weight during operation
29 kg (63.9 lb)
Drain pump capacity
Max. 0.9 L/min. (0.24 gal/min), max. lift: 800 mm (31.5 in) when located 1200 mm (47.2 in) from ceiling surface
Max. instantaneous waste water
discharge volume
Approx. 0.9 L/min. (0.24 gal/min), instantaneous volume when drain pump starts operation
Electrical characteristics
Voltage allowance range
Within ±10% range
Insulation resistance
100 M Ω or greater
Dielectric strength
1000 VAC for 1 min . with no abnormal voltage application
Safety protection functions
(1) Drain pan high water level detection (operation stopped, alarm indicator lamp illuminates)
(2) Detection of water leakage (operation stopped, alarm indicator lamp illuminates)
(3) Detection of water solenoid valve leakage (operation stopped, alarm indicator lamp illuminates)
(4) Drain error detection in waste water drainage pump (operation stopped, alarm indicator lamp illuminates)
Health and sanitation measures
(1) Drying operation function: fan operated to dry humidification module, stops automatically after approx. 2 hours.
This product dries the media cassette following cessation of unit operation (stopped via the remote controller or external
control signal input) in order to ensure hygienic air conditioning operations. The remote controller’s drying operation indicator
light illuminates during drying operation.
(2) Periodic drying function: automatically forces humidification module drying operations when necessary in accordance with
operating conditions.
When the humidifier unit is operated 24 hours a day, forced humidification module drying will be carried out once every 24
hours (approx.) to prevent unpleasant odours and other problems. The drying operation indicator light does not illuminate
during these operations.
Starting/Stopping Operation
When using a humidistat, humidifier operation starts and stops automatically in response to humidity level signals.
When using external control, manual starting and stopping is carried out via the remote controller or external control signal
input from a remote location (external command control), which are processed as second-Input priority.
External control signal inputs include steady-state input signals and instantaneous input signals.
Changing of the humidifier main unit’s control unit DIP switch settings may be required depending on signal type used (set
for steady-state input signals as default in newly shipped products).
External signal output
(1) Operation signal output: no-voltage contact output (arbeit contact, 125 V / 3 A resistive load), output via power indicator
light or humidification indicator light (set to power indicator light output as default in newly shipped products)
(2) Alarm signal output: no-voltage contact output (arbeit contact, 125 V / 3 A resistive load), self-holding
During address setting
Address setting is required when connecting the humidifier main unit(s) and remote controller.
The remote controller’s automatic address setting function detects the number of connected humidifier main units and
completes settings.
(The number of connected units can be confirmed by operating the remote controller and checking the number of blinks
which indicates the number of connected units.)
Remote Controller (with Humidistat)
Settings
Ambient temp. and humidity
5°C–40°C (no freezing), 30%–90% RH (no condensation)
Indoor use only.
Set humidity level range
35%–70% RH, 5% increments
The humidistat level for newly shipped products is set at 40% RH.
Hysteresis
-5% RH
Table 12: