Operating Instructions (GB)
900 191 - V1.0
_________________________________________________________________________________
Page 32
10.3.2
General infeed settings
Function
Explanation
Run-on time feed
1 – 999 seconds
0 seconds > function off
After exceeding the setpoint level, the infeed remains open for the set
time.
Blocking time feed
1 – 999 seconds
0 seconds > function off
After the end of the infeed process, it remains blocked for the set time.
Max. manual infeed operation
1 – 120 seconds
0 seconds > function off
In this menu item the max. runtime for “Manual on” can be set for the
infeed function.
See Chapter 7.1
Max. runtime
1 - 9999 minutes.
0 minutes > function off
0000min Alarm: If the infeed function runs longer than the entered time
without interruption, an alarm
Infeed runtime
is triggered.
The water infeed remains open. If the infeed is stopped, the alarm also
stops.
0000min stop: If the infeed function runs longer than the entered time
without interruption, an alarm
Infeed runtime
is triggered.
The water infeed is stopped. The infeed will not continue until the error
has been manually acknowledged on the control system.
If valves are not used for a longer period of time, they may be stuck the next time they are started.
A quick start-up for the pump(s) can be set in the following menu items. If the valves have not been operated
during the set time, they are put into operation for the set number of seconds. An intermediate infeed process
resets the time counter.
Attention! Exceeding the maximum water level does not switch off this function.
Flooding may result!
Quick start every...
1 – 9999 hours
0 hours > function off
Set the waiting time in hours after which the forced start-up is to take
place.
Quick start for...
1 – 9999 seconds
After the waiting time has expired, the valves are activated for the set
time.