C o n e r g y IP G s t r in g in v e r t e r s e r ie s
In st ru c t io n m an u al
2 7
5 T r a n s p o r t a n d in s t a lla t io n
E
N
G
L
IS
H
Distances
Observe the following distances during installation:
| 300 mm above
| 300 mm below
| 150 mm to the side
| 40 mm from the wall
The 40 mm distance from the wall is ensured by using the
wall bracket supplied.
WARNING!
Risk of fire.
| Do not expose the inverter to highly inflammable gases.
| No highly inflammable liquids should be stored in the
vicinity of the inverter.
| The foundation for installation must be made from a flame-
retardant material.
CAUTION
Air circulation
In order to enable the inverter to be cooled by the ambient air,
it must be installed vertically.
No equipment
may be installed
above or below the inverter.
| Do
not
install string inverters one above the other.