Connected AirWits IAQ

R1.1

AirWits IAQ

Connected AirWits IAQ is a connected total volatile 
organic  compounds,  temperature,  and  humidity 
metering  device  for  real  and  accurate  air  quality 
monitoring.

Last updated J

uly

 

2020

Summary of Contents for AirWits IAQ R1.1

Page 1: ...User Manual Connected AirWits IAQ R1 1 AirWits IAQ Connected AirWits IAQ is a connected total volatile organic compounds temperature and humidity metering device for real and accurate air quality monitoring Last updated July 2020 ...

Page 2: ...Using this manual Read me first About the device Function Assembling and Installation Replacing batteries Uplink Payload description Downlink Downlink Payload Description Troubleshooting Technical Specification Appendix 1 Downlink Message 14 ...

Page 3: ...l and all safety instructions to ensure safe and proper use The descriptions in this manual are based on the default settings of your device The images used in this manual may differ from the actual product The contents of this manual may differ from software provided by service providers or carriers and are subject to change without prior notice Access the Connected Inventions website www connected...

Page 4: ...nual for future reference In case of malfunction deliver the device to the supplier Do not open the cover Do not remove packing material and do not repack the device unless necessary Contact the shipping agent before transportation Inside the device there is a battery which contains approximately 3 0 g of lithium Return the device to a disposal station which collects electronics waste and batterie...

Page 5: ...rld wide Sigfox IoT network connectivity for data transmission enabling very low lifetime cost The installation of the device is extremely simple procedure and requires neither special tools nor configuration operation The device is maintenance free and thus a great solution especially for long term indoor air quality metering It provides accurate data for energy savings and comfortable living cond...

Page 6: ...n case downlink message is not configured the reconfigure bit is 0 or the downlink message cannot be read the previous settings will remain The transmission interval time and adaptive power control function can be set through downlink message After the downlink request the device sends only uplink messages for the next 24 hours After every 24 hours the device will send downlink request again within ...

Page 7: ...ifier and the key of the device The identifier and the PAC key are on the label on the bottom of the device You can also read the identifier and the PAC key using the QR code Switch the device on sliding the power switch to position 1 1 2 7 ...

Page 8: ...e wall having the pins meeting installation holes in the device Please note Avoid placing device closer than 15cm f r o m a n y m e t a l o r magnetic object electric cables electric devices or selective glass as this will dramatically reduce radio performance as well as battery life of the device 4 8 Please note the orientation 3 ...

Page 9: ...nt16 max TVOC Maximum TVOC level between send intervals ppb 8 9 0 15 UInt16 average TVOC Average TVOC level between send intervals ppb Replacing Batteries Please NOTE The device uses battery pack proprietary made If the battery is considered dead please contact Connected Inventions support for the replacement Do not try to replace the battery with other brands available as there is a great risk of...

Page 10: ...0f 271Dec 271 ppb 0x005e 94Dec 94 ppb Min TVOC Avg TVOC Max TVOC 0x2C026F34005e010f00b5 0x026F 623Dec 623 10 40 22 3 C 0x34 52Dec 52 0x2C 00101100Bin Full power TRUE Active power control On FW Version 2 Header Temperature Humidity ...

Page 11: ...its if the carbon dioxide level has exceeded the threshold or the temperature or the humidity have changed more than the threshold after the previous transmission Check that the new settings are valid before applying them The measurement interval cannot be longer than the transmission interval The transmission interval must be multiple of the measurement interval If the new settings are not valid ...

Page 12: ...erground location and other obstacles can dramatically reduce radio signal Check the operation mode of the device Incorrect downlink configuration will affect the behaviour of the product Ensure the configuration is properly done connectedfinland connected_fin connectedinventions www connectedinventions com 358 103115800 Connected Inventions Spektri Business Park Kvintti Building Metsänneidonkuja 12 02...

Page 13: ...th 30 min measuring interval Sensirion SHTC3 Sensirion SGPC3 Temperature 0 50 C Humidity 0 95 TVOC 0 60 000 PPB Sigfox 868 MHz RCZ1 902 MHz RCZ2 920 MHz RCZ4 Internal helical antenna Uplink Downlink Radio configurations Antenna Communication Certification Product Code FCC CE Sigfox Class 0U P_010A_62CF_01 RCZ1 P_010A_4110_01 RCZ2 P_010A_8154_01 RCZ4 CIIAQ 3016 R0101 RCZ1 CIIAQ 3216 R0101 RCZ2 CIIAQ ...

Page 14: ...0000000 C026000000000000 0 205 8027000000000000 C027000000000000 0 210 8028000000000000 C028000000000000 0 215 8029000000000000 C029000000000000 0 220 802A000000000000 C02A000000000000 0 225 802B000000000000 C02B000000000000 0 230 802C000000000000 C02C000000000000 0 235 802D000000000000 0 C02D000000000000 0 240 802E000000000000 C02E000000000000 0 245 802F000000000000 C02F000000000000 0 250 8030000...

Page 15: ...C07D000000000000 0 640 807E000000000000 C07E000000000000 0 645 807F000000000000 C07F000000000000 0 650 8080000000000000 C080000000000000 0 655 8081000000000000 C081000000000000 0 660 8082000000000000 C082000000000000 0 665 8083000000000000 C083000000000000 0 670 8084000000000000 C084000000000000 0 675 8085000000000000 C085000000000000 0 680 8086000000000000 C086000000000000 0 685 8087000000000000 ...

Page 16: ...0 0 1075 80D5000000000000 0 C0D5000000000000 0 1080 80D6000000000000 0 C0D6000000000000 0 1085 80D7000000000000 0 C0D7000000000000 0 1090 80D8000000000000 0 C0D8000000000000 0 1095 80D9000000000000 0 C0D9000000000000 0 1100 80DA000000000000 0 C0DA000000000000 0 1105 80DB000000000000 0 C0DB000000000000 00 1110 80DC00000000000 0 C0DC000000000000 00 1115 80DD00000000000 0 C0DD000000000000 00 1120 80D...

Reviews: