1 Calibration Instruction for Salwico ST200 and
Salwico ST600EX
Calibration Instruction
2
5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C
•
A small terminal screw driver, with thin straight tip.
•
A multimeter with mA (milliampere) capacity.
1.2 Prerequisites
1
Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the
right arrow key to access the
menu tree.
2
Scroll to
4 Gas Detectors
and press
Continue
.
3
Scroll to the detector that should be
calibrated and press
Options
.
4
Scroll to
3 Disable
and choose
Continue
.
5
You have to confirm the disablement before
you can proceed.
Press
Disable
to continue.
6
You will get a confirmation message that
the detector has been disabled.
Press
Close
to continue.
7
If the ambient air is NOT considered
reliable to use to set the ZERO, apply a
clean source of zero gas or compressed air.
8
NOTE!
For the following steps in the
zero calibration instruction
proceed to the Salwico ST200 or
ST600EX detector.