background image

Calibration Instruction

1 Calibration Instruction for Salwico ST600EX-IR

and Salwico ST700IR

5103027_Salwico ST600EX-IR & Salwico ST700IR_Calibration Instruction_I0_EN_2019_C

1

1 Calibration Instruction for Salwico
ST600EX-IR and Salwico ST700IR

1.1 Preliminaries

This instructions applies to the following products:

Figure 1. Salwico ST600EX-IR. Part No. 4483 and 4484.

Figure 2. Salwico ST700IR. Part No. 4482.

Consilium Replacement Sensor 004483 is suitable for ST600EX-IR and ST700IR.

1.2 Prerequisites

1

Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the

right arrow key to access the

menu tree.

Summary of Contents for Salwico ST600EX-IR

Page 1: ...Salwico ST600EX IR Salwico ST700IR CGD50 500 Calibration Instruction ...

Page 2: ...sion without notice due to continued progress in methodology design and manufacturing Consilium Building Safety AB assumes no legal responsibility for any error or damage resulting from the usage of this document April 2019 Document no 5103027_Salwico ST600EX IR Salwico ST700IR_Calibration Instruction_I0_EN_2019_C Part no 5103027 Copyright 2019 Consilium Building Safety AB ...

Page 3: ...ST600EX IR and Salwico ST700IR 1 1 Preliminaries This instructions applies to the following products Figure 1 Salwico ST600EX IR Part No 4483 and 4484 Figure 2 Salwico ST700IR Part No 4482 Consilium Replacement Sensor 004483 is suitable for ST600EX IR and ST700IR 1 2 Prerequisites 1 Use the arrow keys on the control panel to manoeuvre through the different menus Press the right arrow key to access...

Page 4: ...e that the detector has been disabled Press Close to continue 7 If the ambient air is NOT considered reliable to use to set the ZERO apply a clean source of zero gas or compressed air 8 NOTE For the following steps in the zero calibration instruction proceed to the Salwico ST600EX IR or ST700IR detector 9 Remove the cover from the detector The calibration push buttons is situated at the PCB below ...

Page 5: ...al times and wait a little to make sure the reading is stable for half a minute or so 7 Press SW4 MENU The display will return to its standard mode operation after displaying some numbers for the calibration factor 1 4 Calibrating the sensor Span calibration 1 Push SW4 on the detector calibration push buttons to access the user menus The display shows PASS 2 Push once SW3 and twice SW2 to insert t...

Page 6: ...r more for the reading to stabilize 10 Remove the calibration gas and wait until the gas has disappeared and the reading is back 11 Press SW1 MENU The display will after displaying some figures corresponding to sensor factor curves return to its standard mode operation again and the correct mA signal will be sent out You can also press SW1 while gas is still flowing and reading is high but the det...

Page 7: ...Calibration Instruction 1 Calibration Instruction for Salwico ST600EX IR and Salwico ST700IR 5103027_Salwico ST600EX IR Salwico ST700IR_Calibration Instruction_I0_EN_2019_C 5 ...

Page 8: ...ologies for the marine oil and gas transport and building sectors Our commitment goes beyond the products We protect the lives of mothers and fathers sisters and brothers colleagues and friends With representation in more than 25 countries in all time zones we are always close to you www consilium se ...

Reviews: