Installation Environment Requirements
Item
Description
Operating ambient temperature
-20 - +60°C (Vertical installation)
-20 to +55°C with a vertical installation at an angle of 90° to the
left/right or with a horizontal installation.
Operating ambient humidity
10 - 90%RH (No condensation)
Non-operating ambient
temperature
-20 - +60°C
Non-operating ambient humidity 10 - 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Line-noise
resistance
Line noise
Signal Line /±1kV (IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
Static electricity
resistance
Touch /±4kV (IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
Air /±8kV (IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
Vibration
resistance
Sweep
resistance
10 - 57Hz *1 /semi-amplitude vibration 0.15mm, 57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions (JIS C60068-2-6-compliant,
IEC60068-2-6-compliant)
Shock resistance
15G half-sine shock for 11ms in X, Y, and Z directions
(JIS C 60068-2-27 –compliant, IEC 60068-2-27 -compliant)
Standard
VCCI Class A, FCC Class A,
CE Marking (EMC Directive Class A, RoHS Directive)
*1 With the optional DIN rail fitting power supply: 10 - 55Hz (for details, see the user’s guide of the