Application manual for YRB-4EML-31S safety relay
Contrinex AG Industrial Electronics
26
Function description
Start
Action
Result
Diagnostics
1. Unlock emergency stop
button S1.
The emergency stop button closes enable circuit S11,
S12, and S22 of the safety relay.
The circuit is enabled via the reset button.
Power
K1
K2
2. Press reset button S2.
Contactors K3 and K4 are activated and the mirror
contacts (N/C contacts of K3 and K4) in the reset circuit
are opened.
Power
K1
K2
Stop
Action
Result
Diagnostics
1. Press emergency stop
button S1.
The safety function is triggered and contactors K3 and
K4 are opened.
In the reset circuit, the mirror contacts of K3 and K4 are
closed.
Power
K1
K2
Notes on the application
example
1. The emergency stop control device is positive opening according to EN 60947-5-1.
2. Contactors K3 and K4 have mirror contacts according to EN 60947-4-1.
3. Stop category 0 describes an immediate stop by removal of power by interrupting a
machine or drive element according to EN 60204.
4. When using the safety relay, take into consideration the maximum permissible number
of cycles for observing the SIL/PL safety characteristics in the specific application. The
safety characteristics can be found in the FUNCTIONAL SAFETY
CHARACTERISTICS data sheet or the SISTEMA library.