WIRING DIAGRAM

 

 

 

 

 

 

L

  EXTERNAL LIMITS 

FUEL VALVE

 

 
01

  POWER SUPPLY – PHASE 

 

02

  POWER SUPPLY – NEUTRAL 

N

 

03

 

OUTPUT BURNER LOCKOU

 

04

  INPUT REMOTE RESET 

 

05

  FUEL VALVE – NEUTRAL 

N

 

06

  FUEL VALVE – PHASE 

V

 

07

  IGNITION TRANSFORMER – NEUTRAL 

N

 

08

  IGNITION TRANSFORMER – PHASE 

09

  GROUND 

GND

 

10

  FLAME DETECTOR INPUT 

ROD

 

 

FLAME DETECTED ONLY IF THE NEUTRAL IS WIRED 

TO TERMINAL 2 AND CONNECTED TO GROUND

 

 

 

RESET 

 

A reset action is supposed to be a clear defined manual action. An automatic reset is not allowed by EN 13611:2015.

 

FIRO limits the maximum number of remote resets 

(input terminal 4) to 5 actions within a span of 15 minutes.

 

Lockout (resettable only from local button) exceeding this limit. 

 

STATUS DISPLAY 

 

The STATUS DISPLAY 

[4] 

gives, at any time, a clear indication about the working conditions of both the burner and 

the equipment, making it easier to detect any failure occurring in the system or the device.  

 

LOCKOUTS 

 

 

STANDBY 

WAITING FOR RESET WHEN PROGRAMMED 

FOR STANDBY MODE AT 

POWER-ON.

 

   

 

IGNITION FAILURE 

NO FLAME DETECTED AT THE END OF 

SAFETY TIME (IGNITION TRIAL).

 

 

FLAME SIMULATION 

FLAME DETECTION DURING PREPURGE OR 

POSTPURGE (AFTER POS

TCOMBUSTION).

 

   

 

FLAME FAILURE 

FLAME QUENCHING DURING NORMAL 

BURNER OPERATION.

 

 

RESET / COMMAND ERROR 

TOO MANY REMOTE RESETS  

(MORE THAN 5 WITH

IN 15 MIN).

 

   

 

 

 

 

 

CYCLE

 

 

 

MANUAL SHUTDOWN 

UNIT 

HAS BEEN PUT OUT OF 

SERVICE FROM 

PUSH BUTTON. PUSH AG

AIN TO RESTORE. 

   

 

BURNER ON 

FUEL VALVE IS OPEN, OPERATING POSITION 

FOR SINGLE STAGE BUR

NERS.

 

 

PREPURGE 

PURGE OF COMBUSTION CHAMBER OR MIN 

TIME FOR ILLEGAL FLAME PROVING.

 

   

 

POSTCOMBUSTION 

WAITING FOR FLAME QUENCHING AFTER 

LOCKOUT OR SHUTDOWN REQUEST.

 

 

IGNITION 

SAFETY TIME. BURNER 

IGNITION TRIAL 

WITH PILOT FUEL VALVE OPEN.

 

   

 

POSTPURGE 

PURGE OF COMBUSTION CHAMBER, SHOWN 

TOGETHER WITH ASSOCIATED CODE. 

 

Summary of Contents for FIRO

Page 1: ...y devices The device is not user serviceable a faulty device must be put out of order and sent back for servicing CONTRIVE manufactures products used as components in a wide variety of industrial syst...

Page 2: ...RNAL NON REPLACEABLE 5A SAFETY FUSE STATUS DISPLAY 4 USE POWER SIGNAL AND CONTROL CABLE SUITABLE FOR THE TYPE OF OPERATION AND COMPLYING WITH ALL REGULATIONS DO NOT ROUTE CONNECTIONS TOGETHER WITH FRE...

Page 3: ...cation about the working conditions of both the burner and the equipment making it easier to detect any failure occurring in the system or the device LOCKOUTS STANDBY WAITING FOR RESET WHEN PROGRAMMED...

Page 4: ...OUTPUTS RELEASED RESET FAILURE PUSH BUTTON OR REMOTE RESET ACTIVE FOR LONG TIME MORE THAN 10 SECONDS 1 A PREMANENT FAILURE TO THE RELAY CONTACT MAY CAUSE THE MAIN FUSE TO BLOWN AS A SAFETY MEASURE TO...

Page 5: ...124 4 Set pre purge time in forced draught burners according to applicable and relevant standards EN 676 During this time the flame simulation test is carried out This is a merely waiting time if the...

Page 6: ...evant application standards default for EN 298 is 1 and must not exceed 5 including valves closing time for EN 746 2 509 ALLOWED POST COMBUSTION TIME Flame signal allowed for 20 once fuel valves has b...

Page 7: ...FOR PG9 CABLE GLANDS FRA CAST ALUMINUM ALLOY EN AB 46100 IP64 OVERALL DIMENSION 200 x 120 x 71 mm WEIGHT 850 g ELECTROSTATIC POLYESTER POWDER COATING RAL9006 FRP THERMOPLASTIC POLYMER BLEND UL V0 IP64...

Page 8: ...if the safety is not impaired Push the front panel button to reset from lockout will take place at release Flame quenching during burner operation will force the system to lockout recycle or ignition...

Page 9: ...Y II PURSUANT TO EN 60730 FLAME DETECTION MINIMUM IONIZATION CURRENT 1 A CURRENT LIMITATION 1 mA DETECTOR LINE LENGTH 30 m SINGLE ROD LINE LENGTH 2 m DETECTOR VOLTAGE 250 Vac DETECTOR INSULATION 50 M...

Reviews: