PROGRAM SEQUENCE 

 

 

A

  SELF TEST

  IS  PERFORMED  AT POWER-ON, ONCE 

SUCCESSFULLY COMPLET

ED BURNER IS READY T

O START. 

 

 

IF THE UNIT HAS BEEN

 TURNED OFF WHILE IN 

LOCKOUT

 

OR PARAMETER 101 HAS

 

BEEN SET TO 

STANDBY

, IT WILL 

BE NECESSARY TO 

PUSH THE LOCAL OR REMOTE 

BUTTO

TO EXIT FROM NON-VOLATILE LOCKOUT. 

 

FLAME SIMULATION

  VERIFIED WHILE IN  WAITING OR 

PREPURGE. 

 

 

 

AFTER PRESET 

WAITING OR PREPURGE

  TIME HAS 

ELAPSED, IGNITION DEVICE   ACTIVATED  AND VERIFIED, 

THEN THE GAS VALVE IS OPEN.  

 

 

 

BURNER

  PROVING STARTS IF THE  FLAME IS DETECTED 

WITHIN THE 

SAFETY TIME

.  

 

 

 

IF NO FLAME IS DETECTED WITHIN THE SAFETY TIME, A 

LOCKOUT OCCURS. 

DEPENDING ON PARAMET

ER  403  THE  U

NIT COULD 

CARRY OUT UP TO THREE  FURTHER 

START-UP 

ATTEMPTS

 

AFTER THE 

BURNER

  PROVING THE IGNITION CYCLE IS 

COMPLETED AND BURNER

 IS ON. 

 

 

FLAME FAILURE

 DURING OPERATION LEADS TO LOCKOUT, IGNITION RESTORATION OR RECYCLE (PARAMETER 

504).

 

 

 

 

 

MANUAL  SHUTDOWN REQUEST

 

WILL  TURN  OFF  THE  BU

RNER, WAITING FOR AL

LOWED  POSTCOMBUSTION

  AND OPTIONAL 

POSTPURGE, 

BURNER CAN BE SWITCH

ED OFF REMOVING THE POWER SUPPLY.

 

 
 

 

 

 

TECHNICAL DATA 

 

POWER SUPPLY 

 

 VOLTAGE 

230 V +10

-

15%

 

 FREQUENCY 

50/60 Hz

 

 LINE FUSE 

3 A 

QUICK-ACTING - 5x20mm

 

 POWER CONSUMPTION 

4 VA 

MAX 

 POWER DISSIPATION 

3 W 

MAX

 

 

OVERVOLTAGE CATEGORY 

II PURSUANT TO EN 60

730 

 

FLAME DETECTION 

 

MINIMUM IONIZATION CURRENT 

1

 

µ

CURRENT LIMITATION 

 

< 1 mA

 

DETECTOR LINE LENGTH 

< 30 m 

SINGLE ROD LINE LENGTH 

< 2 m 

DETECTOR VOLTAGE 

250 Vac  

DETECTOR INSULATION 

> 50 M

Ω 

ENVIRONMENT

 

 

OPERATING TEMPERATURE 

(-

4 … 140 °F)  

-

20 … 60 °C

 

STORAGE TEMPERATURE 

(-

40 … 185 °F)  

-

40 … 85 °C

 

RELATIVE HUMIDITY 

NO CONDENSATION ALLOWED   

WEIGHT 

≈ 

880 g 

ALUMINIUM

 | 

≈ 

550 g 

PLASTIC

  

PROTECTION CLASS 

IP64 

NEMA3

 

MOUNTING POSITION 

ANY 

 

THIS UNIT IS NOT INTENDED FOR EXPLOSIVE OR CORROSIVE ENVIRONMENTS 

 

OUTPUTS 

 

MAX RATED VOLTAGE 

250 Vac 

MAX SWITCHING VOLTAGE 

440 Vac 

 

MAX LOAD (PER OUTPUT) 

2 A cos

ϕ

=0,7 

 

 

 

 

 

 

CONTRIVE S.r.l.  I-

24040 SUISIO (Bergamo) via Enrico Fermi 18

 

 

 

ANY ILLUSTRATIONS, PHOTOGRAPHS, OR EXAMPLES USED IN THIS MANUAL ARE PROVIDED AS EXAMPLES ONLY AND MAY NOT APPLY TO ALL PRODUCTS TO 

WHICH THIS MANUAL IS AP

PLICABLE.  THE  PRODUC

TS AND SPECIFICATION

S  DESCRIBED  IN  THIS 

MANUAL OR THE CONTENT AND PRESENTATION OF THE 

MANUAL MAY BE CHANGE

D WITHOUT NOTICE TO IMPROVE THE PRODUCT AND/OR THE MANUAL. 

PRODUCT NAMES, CORPORATE NAMES, OR TITLES USED WITHIN THIS DOCUMENT MAY 

BE TRADEMARKS OR REG

ISTERED TRADEMARKS OF OTHER COMPANIES, 

AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THE READER

S’ BENEFIT, AND WITH

OUT INTENTION TO INFRINGE. 

WHILE EVERY EFFORT H

AS BEEN MADE TO MAKE

 SURE THE INFORMATION IN THIS DOCUMENT IS CORRECT, CONTRIVE CAN NOT 

BE LIABLE FOR ANY DA

MAGES 

WHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT. 

 

© COPYRIGHT 2020 CONTRIVE SRL ITALY. ALL RIGHT RESERVED.

 

Summary of Contents for FIRO

Page 1: ...y devices The device is not user serviceable a faulty device must be put out of order and sent back for servicing CONTRIVE manufactures products used as components in a wide variety of industrial syst...

Page 2: ...RNAL NON REPLACEABLE 5A SAFETY FUSE STATUS DISPLAY 4 USE POWER SIGNAL AND CONTROL CABLE SUITABLE FOR THE TYPE OF OPERATION AND COMPLYING WITH ALL REGULATIONS DO NOT ROUTE CONNECTIONS TOGETHER WITH FRE...

Page 3: ...cation about the working conditions of both the burner and the equipment making it easier to detect any failure occurring in the system or the device LOCKOUTS STANDBY WAITING FOR RESET WHEN PROGRAMMED...

Page 4: ...OUTPUTS RELEASED RESET FAILURE PUSH BUTTON OR REMOTE RESET ACTIVE FOR LONG TIME MORE THAN 10 SECONDS 1 A PREMANENT FAILURE TO THE RELAY CONTACT MAY CAUSE THE MAIN FUSE TO BLOWN AS A SAFETY MEASURE TO...

Page 5: ...124 4 Set pre purge time in forced draught burners according to applicable and relevant standards EN 676 During this time the flame simulation test is carried out This is a merely waiting time if the...

Page 6: ...evant application standards default for EN 298 is 1 and must not exceed 5 including valves closing time for EN 746 2 509 ALLOWED POST COMBUSTION TIME Flame signal allowed for 20 once fuel valves has b...

Page 7: ...FOR PG9 CABLE GLANDS FRA CAST ALUMINUM ALLOY EN AB 46100 IP64 OVERALL DIMENSION 200 x 120 x 71 mm WEIGHT 850 g ELECTROSTATIC POLYESTER POWDER COATING RAL9006 FRP THERMOPLASTIC POLYMER BLEND UL V0 IP64...

Page 8: ...if the safety is not impaired Push the front panel button to reset from lockout will take place at release Flame quenching during burner operation will force the system to lockout recycle or ignition...

Page 9: ...Y II PURSUANT TO EN 60730 FLAME DETECTION MINIMUM IONIZATION CURRENT 1 A CURRENT LIMITATION 1 mA DETECTOR LINE LENGTH 30 m SINGLE ROD LINE LENGTH 2 m DETECTOR VOLTAGE 250 Vac DETECTOR INSULATION 50 M...

Reviews: