background image

© 2000 CONTRIVE • B14

50.EN  

06

1

7

 

1

 

www.contrive.it 

 

 

UV4

 SH

 

HIGH PERFORMANCE UV FLAME DETECTOR 

 

 

 

UV4

SH

 is an high performance selected UV detector that can be 

used for flame detection in gas, oil and mixed burners together 

with suitable Burner Control Unit or Flame Amplifier Device.

 

The core component is a glass bulb filled with gas, containing 

two electrodes. When appropriate voltage is applied between 

electrodes, if an ultraviolet electromagnetic radiation hits the 

phototube, electrons emitted by negative biased electrode can 

be captured by positive biased electrode, starting an ionization 

process leading an electric discharge between electrodes 

producing a current flow. 

UV4

SH

 is a compact unit for industrial use, the body is made by 

thermal isolating material to avoid sensor overheating when 

applied on the burner head. 

When the temperature at peepsight exceed 70°C it's advisable 

to add a ¾” pipe spacer 

(up to 40 cm) 

between the burner and 

the sensor and apply a cooling filtered air flow to the special 

connection provided on the side of the probe. 

Although  UV4SH  is  blind  to  sunlight,  some  discharge  lamps 

produces UV emission that can be detected by the phototube.  

 

 

 

SAFETY INFORMATION 

 

Read and understand this manual before installing, operating, or servicing this unit.  This unit must be installed 

according to this manual and local regulations. The drawings may show units without covers or safety shields to 

illustrate details. 

Disconnect power supply and follow all usual safety precautions before carrying out any operation 

on the device. 

Be sure to reinstall covers or shields b

efore operating any devices. 

The device is not user serviceable, a faulty device must be put out of order and sent back for servicing. 

 

CONTRIVE manufactures products used as components in a wide variety of industrial systems and equipment. The 

selection and application of products remain the responsibility of the equipment manufacturer or end user. 

CONTRIVE accepts no responsibility for the way its products are incorporated into the final system design. 

All 

systems or equipment designed to incorporate a product manufactured by CONTRIVE must be supplied to the end 

user with appropriate warnings and instructions as to the safe use and operation of that part. 

Any warnings provided by CONTRIVE must be pro

mptly provided to the end user. 

 

CONTRIVE guarantees for two years from the date of manufacture of its product to replace, or, at its option, to 

repair any product or part thereof (except fuses and with some limitations for tubes and photocells) which is found 

defective in material or workmanship or which otherwise fails to conform to the description of its sales order. 

CONTRIVE makes no warranty of merchantability or any other warranty express or implied. CONTRIVE assumes no 

liability for any personal injury, property damage, losses, or claims arising from misapplication of its products. 

 

 

RECEIVING 

 

Please perform the following tasks after receiving the product: 

 

Inspect the unit for damage.  If the product appears damaged upon receipt, contact the shipper immediately. 

 

If you have received the wrong model or the device does not function properly, contact your supplier. 

 

Store the product in a dry place, see technical specification for temperature limit. 

 

 