WIRING DIAGRAM
1
PO
SITIVE TERMINAL
USUALLY CONNECTED TO
GROUND
2
NEGATIVE TERMINAL
USUALLY CONNECTED TO
AMPLIFIER INPUT
CONNECTION WITH
REVERSED POLARITY DOES NOT DAMAGE
THE DETECTOR BUT PRODUCES NO USEFUL FLAME SIGNAL
CLASS II DEVICE
CONNECTION TO PROTEC
TION GROUND IS NOT REQUIRED
TECHNICAL DATA
SPECTRAL RESPONSE
185 … 260 nm
OPERATING VOLTAGE
200 … 280 V
AC
DISCHARGE CURRENT
1 mA
PEAK DISCHARGE CURRENT
30 mA
RECOVERY TIME
2Oµs
@ 10% DUTY CYCLE
OPERATING TEMPERATURE
-
20 … +
90°C
UV TUBE TEMPERATURE
125°C
MAX
PROTECTION CLASS
IP65
OPERATING LIFE
1
> 10.000 hours
@ 50°C / 1mA
VIBRATION
0,5 G
MAX
RELATIVE HUMIDITY
NON CONDENSING
10 … 90%
MOUNTING POSITION
2
ANY
1
WEIGHT
150 g
MAX
1
UP TO 100.000 hours @25°C
2
DO NOT INSTALL ON TOP IN VERTICAL POSITION WHEN
COMBUSTION PRODUCTS CAN FILL THE VOLUME IN FRONT
OF THE SENSOR
DIMENSIONS
THERMAL INSULATING CASE Ø
35 x
80
mm
1
DIN43650
–
ISO4400 CONNECTOR
2 POLES + EARTH
–
PG11
2
DIN43650
–
ISO4400 SOCKET
2 POLES + EARTH
3
OPTIONAL COOLING
CONNECTION ¼“
4
BURNER HEAD
CONNECTION ¾”
FRONT SIDE OF THE SENSOR IS SEALED WITH EPOXY RESIN
THERE IS NO NEED FOR
ADDITIONAL QUARTZ GLASS