Specifications 

 

3.1

 

Technical Specifications

 

 

Item 

Description 

 

Power requirements 

110 or 220 VAC ± 10%, 60/50 Hz,  20VA 

Dimensions 

(HxWxD) 96x96x80 mm 

Shipping Weight 

514 gr. 

Voltage limits 

1000VAC 

Current limits 

50A 

Enclosure material 

ABS + Antiflame 

Operating temperature 

-20 - + 70 C 

Storage temperature 

-20 - + 80 C 

Humidity 

0- 90 RH% 

Voltage input terminals 

VL – E10 1708 

Mounting 

Front panel mounting 

Digital Output (optional) 

Dry contact 

 
 
 

3.2

 

Measuring Specifications 

 

Measurement Parameter 

Display Range 

in direct 

connection 

(scaling factor 1) 

Measuring in 

direct 

connection 

(scaling factor 1) 

Display Range 

 

Current 

0.01 – 6A 

0.01 – 6A 

0.01 – 999KA 

Neutral Current 
(calculated ) 

0.01 – 6A 

0.01 – 6A 

0.01 – 999KA 

Voltage L-N 

0.00 – 650 V 

0.00 – 650 V 

0.01 – 999KV 

Voltage L-L 

0.00 – 650 V 

0.00 – 650 V 

0.01 – 999KV 

Frequency (Hz) 

45.1-65.1 Hz 

45.1-65.1 Hz 

45.1-65.1 Hz 

Active power total\phase 

 

 

0.00W – 999KW 

Reactive power 
total\phase  

 

 

0.00VAR -

999KVAR 

Apparent power 
total\phase 

 

 

0.00VA -

999KVA 

Power Factor (cap.\ind.) 

-1.00 ÷ 1.00 

-1.00 ÷ 1.00 

-1.00 ÷ 1.00 

 

Summary of Contents for ElNet VIP

Page 1: ...ElNet VIP Current Power Multimeter Rev 1 7...

Page 2: ...5 3 2 Measuring Specifications 5 4 Current transformer ratio settings 6 5 Voltage transformer ratio settings 6 6 Electrical values display 7 7 Electrical values display 7 8 Minimum Maximum values dis...

Page 3: ...insert the VIP Multimeter into the suitable space which is to be prepared in advance Make sure that the device is inserted in the right direction The device has a plastic knob which adjusts itself for...

Page 4: ...4 2 Wiring diagram...

Page 5: ...tput optional Dry contact 3 2 Measuring Specifications Measurement Parameter Display Range in direct connection scaling factor 1 Measuring in direct connection scaling factor 1 Display Range Current 0...

Page 6: ...transformer 5A 4 5 The headline SET will be displayed on the screen on the second line the secondary value of current transformer 5A the third line allows to define the value of the primary current tr...

Page 7: ...r automatically swapping displays click on the V I P and hold for 6 seconds until the automatically swapping mode will begin 7 Electrical values display 7 1 Click on the V I P button each additional c...

Page 8: ...est measured values of voltage and current Hi the next screens present the lowest measured values of voltage and current Lo and then respectively high and low frequency and power factor for each phase...

Page 9: ...the Enter button for about 6 seconds 10 2 2 Use the buttons to change the password to code 21 and press Enter 10 2 3 SET AL will appear and it would be possible to set the min voltage ratio by using t...

Reviews: