No volt relay 

 

10.1

 

General:  

When the voltage is proper (above 50VAC, adjustable) and the 
phases' order is proper the indication relay is closed, as appears 
at the wiring diagram. The maximum current that is possible to 
transfer through this relay is 150ma which is enough to operate 
a regular control relay.  

10.2

 

No volt alarm setting:  

10.2.1

 

In  order  to  set  the  minimum  voltage  value  for  the  no 
volt relay press the "Enter" button for about 6 seconds.  

10.2.2

 

Use the "↑ ↓" buttons to change the password to "code 
21" and press "Enter".  

10.2.3

 

"SET AL" will appear and it would be possible to set 
the min. voltage ratio by using the "↑ ↓". After setting 
this value save it by pressing the "Enter" button. 

 

 

10.3

 

Phase order alarm:  

10.3.1

 

In  order  to  turn  ON/OFF  the  phase  order  relay,  press 
the "Enter" button for about 6 seconds.  

10.3.2

 

Use the "↑ ↓" buttons to "code 31" and press Enter.  

10.3.3

 

The  phase  order  screen  will  appear  and  it  would 

enable  you  to  select  YES/NO  (equivalent  to 
ON/OFF).  After  setting  the  desirable  option  save  it 
by pressing the "Enter" button. 

 

 

 

Summary of Contents for ElNet VIP

Page 1: ...ElNet VIP Current Power Multimeter Rev 1 7...

Page 2: ...5 3 2 Measuring Specifications 5 4 Current transformer ratio settings 6 5 Voltage transformer ratio settings 6 6 Electrical values display 7 7 Electrical values display 7 8 Minimum Maximum values dis...

Page 3: ...insert the VIP Multimeter into the suitable space which is to be prepared in advance Make sure that the device is inserted in the right direction The device has a plastic knob which adjusts itself for...

Page 4: ...4 2 Wiring diagram...

Page 5: ...tput optional Dry contact 3 2 Measuring Specifications Measurement Parameter Display Range in direct connection scaling factor 1 Measuring in direct connection scaling factor 1 Display Range Current 0...

Page 6: ...transformer 5A 4 5 The headline SET will be displayed on the screen on the second line the secondary value of current transformer 5A the third line allows to define the value of the primary current tr...

Page 7: ...r automatically swapping displays click on the V I P and hold for 6 seconds until the automatically swapping mode will begin 7 Electrical values display 7 1 Click on the V I P button each additional c...

Page 8: ...est measured values of voltage and current Hi the next screens present the lowest measured values of voltage and current Lo and then respectively high and low frequency and power factor for each phase...

Page 9: ...the Enter button for about 6 seconds 10 2 2 Use the buttons to change the password to code 21 and press Enter 10 2 3 SET AL will appear and it would be possible to set the min voltage ratio by using t...

Reviews: