No volt relay
10.1
General:
When the voltage is proper (above 50VAC, adjustable) and the
phases' order is proper the indication relay is closed, as appears
at the wiring diagram. The maximum current that is possible to
transfer through this relay is 150ma which is enough to operate
a regular control relay.
10.2
No volt alarm setting:
10.2.1
In order to set the minimum voltage value for the no
volt relay press the "Enter" button for about 6 seconds.
10.2.2
Use the "↑ ↓" buttons to change the password to "code
21" and press "Enter".
10.2.3
"SET AL" will appear and it would be possible to set
the min. voltage ratio by using the "↑ ↓". After setting
this value save it by pressing the "Enter" button.
10.3
Phase order alarm:
10.3.1
In order to turn ON/OFF the phase order relay, press
the "Enter" button for about 6 seconds.
10.3.2
Use the "↑ ↓" buttons to "code 31" and press Enter.
10.3.3
The phase order screen will appear and it would
enable you to select YES/NO (equivalent to
ON/OFF). After setting the desirable option save it
by pressing the "Enter" button.