6
RECEIVING THE UPS
INSPECTION, PLACEMENT, INSTALLATION, SETUP AND
START-UP SHOULD BE PERFORMED BY QUALIFIED
PERSONNEL ONLY
INSPECTION
Upon receipt of the UPS, visually inspect the unit(s) for shipping damage. If shipping damage has occurred, the
purchaser should promptly notify the carrier
and file a claim with the
carrier
. The factory should be notified if the
damages may impair the operation of the unit. Reference front cover or accompanying paper work for factory contact
information.
Note: Open the enclosure(s) and inspect inside the unit for shipping damage.
If it is necessary to store the unit, be sure to place it in a clean dry area.
For extended storage, the batteries must
be charged for 24 hours every 6 months.
Failure to do so will result in weak or bad batteries which WILL
NOT be covered under the warranty.
Charging is accomplished by turning the UPS on and allowing it to run. See
“Start-up Procedure”
for turning the UPS on.
While storing disconnect the battery connector from the UPS.
Make sure proper ventilation is available any time the inverter is on.
Warranty does not cover any defects or damages caused by failure to properly store the Product before
installation, including the charge of batteries if not in use (charged) for more than 6 months. Battery
storage
temperature when not in use is 25°C for 6 months. For each 9°C rise, reduce storage time by half.
IMPORTANT NOTICE
This shipment has been carefully inspected, checked and properly packaged at our company.
When it was delivered to the carrier it was in good condition and technically it became your property
at that time. Thus, any damage, whether obvious or hidden, must be reported to the transportation company
within FIVE days of receipt of the shipment at your premises to avoid forfeiting claims for damages.
FOR ALL SHIPMENTS DAMAGED IN TRANSIT
Leave the items, packing material and carton “AS IS”. Notify your carrier’s local office
and ask for immediate inspection of the carton and contents.
After inspection has been made by the carrier, and you have received acknowledgment in writing as to the
damage, notify our Customer Service Department to make any required repair arrangements.
It is your responsibility to follow the above instructions or the carrier will not honor any claims for damage.
Also, if there are any shortages or questions regarding this shipment, please notify us within FIVE days.
Please note that we cannot be responsible for any service work or back-charges unless authorized
by us in writing, before the work is performed.
WHILE IN STORAGE BATTERIES MUST BE CHARGED
FOR 24 HOURS EVERY 6 MONTHS. WHILE IN STORAGE
DISCONNECT THE BATTERY CONNECTOR FROM THE INVERTER.
STORAGE
Summary of Contents for MODEL ES
Page 51: ...51 APPENDIX A RELATIVE DRAWINGS SCHEMATICS APPENDIX A ...