7
RECEIVING THE UPS CONTINUED
TOOLS REQUIRED
:
1/2” Socket, Forklift, dolly.
***CAUTION***
CABINETS AND BATTERIES ARE EXTREMELY HEAVY
USE PROPER EQUIPMENT WHEN REMOVING
THE CABINETS FROM THE SKID
1. Remove the plastic wrapping and banding and discard.
2. To remove the UPS from the pallet, first remove the four 1/2” lag bolts that are securing the UPS cabinet to the
pallet and remove the piece of wood in the front and back of the UPS that blocks fork lift entry.
3. Using a forklift, place the forks securely under the UPS as shown below.
4. Carefully lift the UPS from the skid.
5. Set the UPS down until you are ready for installation.
REMOVING THE UPS FROM THE PALLET
*****SHOCK HAZARD*****
DO NOT SHORT BATTERY TERMINALS
LIFT UNIT FROM
SKID HERE
CAUTION: DO NOT DAMAGE
CASTERS UNDER UNIT
REMOVE 1/2” LAG BOLTS
(TYPICAL BOTH SIDES)
LIFT TO MOVE HERE
REMOVE
(TYPICAL BOTH SIDES)