27
OPTION INTERCONNECTION DIAGRAM
NOTE: THE POWER SUPPLY FOR DEVICES, EXCLUDING THE REMOTE EMERGENCY POWER OFF, MUST
BE TAKEN FROM THE OUTPUT OF THE UPS. A 120V RECEPTACLE (5-20R) WHOSE SUPPLY IS
TAKEN FROM THE OUTPUT OF THE UPS MUST BE INSTALLED NEAR THE LOCATION OF THE DEVICE.
Refer to the manual or installation documents that accompanied these devices
for function, use and set up instructions.
REAR VIEW OF INVERTER CABINET
1
“T” CABINET
2
REMOTE
EMERGENCY
POWER OFF
(See
accompanying
installation
documents
for this option)
TO K6 PINS 1 - 2
1
REMOTE ANNUNCIATOR
(See accompanying installation
documents for this option)
TO K6
Alarm Silence
Inverter On
Low Battery
On Bypass
On Battery
General Alarm
REMOTE ANNUNCIATOR
Uninterruptible Power Sypply
Uninterruptible Power Sypply
TO UPS
RECEPTACLE
SEE NOTE
BELOW
1
NETMINDER
ADAPTER
(Internal to System)
(See NetMinder
quick start guide
for set up
instructions).
2
TO ETHERNET
RJ45 CABLE
K6
1
“T” CABINET
TERMINAL ORIENTATION
*CONT
ACTS
ARE USER SELECT
ABLE NORMALL
Y OPEN OR NORMALL
Y CLOSED BY
MEANS
OF JUMPERS ON CONTROL
BOARD LOCA
TED JUST
BELOW
THE
TERMINALS
AS SHOWN
ABOVE.
THESE JUMPERS CAN BE
ACCESSED BEHIND INNER DOOR, BEHIND CONTROL
MODULE CLOSEOUT
P
ANEL, ON
THE CONTROL
BOARD.
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
J9
J10
J8
J7
Customer supplied, Normally Open, Dry Contact Input
R.E.P.O.
TEST ACTIVE
LOW BATTERY
ON BATTERY
GENERAL ALARM
+5.5VDC
COMMON
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
CHASSIS GROUND
1
“S” CABINET
2
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
“S” CABINET
TERMINAL ORIENTATION
R.E.P.O.
TEST ACTIVE
LOW BATTERY
ON BATTERY
GENERAL ALARM
+5.5VDC
COMMON
CHASSIS
GROUND
Customer supplied,
Normally Open,
Dry Contact Input
*CONTACTS ARE USER SELECTABLE NORMALLY OPEN OR NORMALLY CLOSED BY MEANS
OF JUMPERS ON CONTROL BOARD LOCATED JUST BELOW THE TERMINALS AS SHOWN
ABOVE. THESE JUMPERS CAN BE ACCESSED BEHIND INNER DOOR, BEHIND CONTROL
MODULE CLOSEOUT PANEL, ON THE CONTROL BOARD.
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
J9
J10
J8
J7
K6
1
REAR VIEW OF INVERTER CABINET
Summary of Contents for MODEL ES
Page 51: ...51 APPENDIX A RELATIVE DRAWINGS SCHEMATICS APPENDIX A ...
Page 57: ...57 NOTES ...