28
DO NOT ATTEMPT TO OPERATE THE
UNIT UNTIL ALL SET UP PROCEDURES HAVE
BEEN COMPLETED
START UP PROCEDURE
1.
Turn off all AC input and output circuit breakers. Verify that there are not any shorts on the input and output cables.
2. Verify the bypass switch is in the “Normal” position.
3. Check the battery connector for proper voltage and polarity.
4.
Verify for correct voltage at the input terminals (H1, H2, HN). This should match the information on the specification
tag on the unit.
5. Connect the battery connector (see
“Appendix A - Cabinet Outlines”
for location).
6. Turn on the AC input breaker.
7.
Press the “On/Off” button located on the Intellistat TS
TM
monitor. After an approximate 10 second delay, the unit
will power up. See
“Operation - Intellistat TS
TM
Monitor Operation”
.
8. Check for correct output voltage at the output terminal (X1, X2, XN).
Note 1
: Output voltage information is located on the specification tag.
9. Turn “
OFF
” the input breaker and verify the system on battery power.
10. Turn “
ON
” the breaker and verify the system returns to normal power.
BEFORE TURNING LOADS ON.
11. Turn the bypass switch to Bypass Mode -See
“Bypass Switch Operation”
.
DO NOT SWITCH WHILE IN BATTERY
MODE.
NOTE:
The module will switch to static bypass. This is normal, wait until the unit returns from static bypass
BEFORE
proceeding. This can be verified by checking the display.
12. Once the unit is out of static bypass, turn on load breakers one at a time. Verify all output voltages and currents.
If output voltages are correct, turn “
OF
F” all load breakers.
13. Turn the bypass switch back to normal mode.
DO NOT SWITCH WHILE IN BATTERY MODE.
NOTE:
The module will switch to static bypass. This is normal, wait until the unit returns from static bypass
BEFORE
proceeding. This can be verified by checking the display.
14. Once the unit is out of static bypass, turn the output load breakers on one at a time and verify that the amount
of load does not exceed the system rating as indicated by the percentage load shown on the front display.
15. Test options as required.
CAUTION - DO NOT PLACE UNIT IN BYPASS WHILE BATTERY TESTING IS IN PROGRESS.
Summary of Contents for MODEL ES