INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

 

YT202, YT202T 

Intelligent Photoelectric Smoke Sensors 

Used instead of Honeywell, System Sensor, Notifier, Johnson Controls 

Convoy Security 

Honeywell 

System Sensor 

Notifier 

Johnson Controls 

YT202 

TC806A1037,TC906 

ZM992, 2251B, 2551 

ND682

SDX-751 

2251J,2551J 

YT202T 

 

2251TB,2551T 

 

 

SPECIFICATIONS 

Operating Voltage Range: 

              15 to 32 VDC 

Standby Current: 

                              300

µ

A @ 24 VDC (one communication every 5 seconds with LED blink enabled)   

Maximum Alarm Current (LED on: )    2.5 mA @ 24 VDC 
Operating Humidity Range:                10% to 93% Relative Humidity, Non-condensing 
Operating Temperature Range: 

      32

°

F to 120

°

F (0

°

C to 49

°

C) 

Heat Sensor:                                          135

°

F Fixed Temperature Electronic Thermistor (only YT202T) 

Height:                                                2.3

˝

 (59 mm) installed in Base 

Diameter:                                              4.1

˝

 (105 mm) 

Weight:                                                4.6 oz. (130 g) 
 

BEFORE INSTALLING 

This  sensor  must  be  installed  in  compliance  with  the 
control panel system installation  manual. The installation 
must  meet  the  requirements  of  the  Authority  Having 
Jurisdiction  (AHJ).  Sensors  offer  maximum  performance 
when  installed  in  compliance  with  the  National  Fire 
Protection Association (NFPA); see NFPA 72. 

GENERAL DESCRIPTION

 

Models YT202, YT202T are plug-in type photoelectronic 
smoke  and  heat  sensors  with  addressable  analog 
communications.  The  sensors  transmit  an  analog 
representation  of  smoke  density  or  temperature  over  a 
communication  line  to  a  control  panel.  Inside  MCU

EEPROM  keep  the  sensor

s  address  that  can  be  set  by  a 

portable Address setting device. 
Two  LEDs  on  the  sensor  are  controlled  by  the  panel  to 
indicate sensor status. 
Models  YT202T  combine  a  photoelectronic  sensing 
chamber  and  135

°

F  (57.2

°

C)  fixed  temperature  heat 

detector. 

The  YT202,  YT202T  require  compatible  addressable 
communications  to  function  properly.  Connect  these 
sensors to listed-compatible control panels only. 

WIRING GUIDE 

All  wiring  must  be  installed  in  compliance  with  the 
National Electrical Code, applicable local codes, and any 
special requirements of the Authority Having Jurisdiction. 
Proper wire gauges should be used. The installation wires 
should  be  color-coded  to  limit  wiring  mistakes  and  ease 
system  troubleshooting.  Improper  connections  will 
prevent a system from responding properly in the event of 
a fire. 

Remove  power  from  the  communication  line  before 
installing sensors. 

1. Wire the sensor base per the wiring diagram, Figure 1. 
2.  Set  the  desired  address  by  portable  address  setting 
device. 

3. Install the sensor into the sensor base. Push the sensor 
into  the  base  while  turning  it  clockwise  to  secure  it  in 
place. 
4.  After  all  sensors  have  been  installed,  apply  power  to 
the control unit and activate the communication line. 
5. Test the sensor(s) as described in the TESTING section 
of this manual. 

 
Figure 1. Wiring diagram: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Dust  covers  provide  limited  protection  against 
airborne  dust  particles  during  shipping.  Dust  covers 
must be removed before the sensors can sense smoke. 
Remove  sensors  prior  to  heavy  remodeling  or 
construction. 

 

TAMPER-RESISTANCE 

Models  YT202,  YT202T  include  a  tamper-resistant 
capability  that  prevents  their  removal  from  the  bracket 
without the use of a tool. 

TESTING 

Before  testing,  notify  the  proper  authorities  that  the 
system  is  undergoing  maintenance,  and  will  temporarily 
be out of service. Disable the system to prevent unwanted 