M100 FireGard
TM
Chain & Crank
02/11
WARNING
1.
CAUTION: Review all installation instructions, procedures, cautions and warnings contained within
this manual prior to installing and/or servicing this product. As with all releasing device systems,
maximum fire protection is provided when installed in accordance with factory specifications and
used with optional fuse link systems.
2.
Installation and testing to factory specifications shall be performed by factory authorized personnel
for proper operation in accordance with all of the latest National Fire Protection Association (NFPA),
Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or
other applicable building and fire standards, guidelines, regulations and codes including, but not
limited to, all appendices and amendments and the requirements of the local Authority Having
Jurisdiction (AHJ).
3.
Installation to be performed by factory authorized door system technicians only.
4. Clear fire door opening and prohibit all traffic through door opening during system testing!
INTRODUCTION
The releasing device is a failsafe constantly energized solenoid mechanism. It is designed for use on
rolling fire doors and counter fire doors. Inside the mechanism, contact relays receive the alarm signal
from the fire alarm control panel. When the unit receives the signal, the power to the solenoid is cut,
releasing the fire door mechanism and hence closing the fire door. The alarm signal can be Form C dry
contact or 24VDC/VAC. A power interruption in excess of 10 seconds will release the solenoid
mechanism. The release has a 10 second delay on alarm, closed door detection capabilities, Form C
relay outputs for the status of release box and 24VDC power output for door close warning.