27
www.coolautomation.com
CooLinkHub PRM 1.0
© 2017 CoolAutomation
ASCII I/F
>
ls
L1.101 ON 25C 24C Low Cool OK - 1
L1.102 ON 22C 23C Med Cool OK - 0
L2.101 ON 25C 27C Low Cool OK - 1
L2.102 OFF 20C 27C High Cool OK - 0
OK
5.3.17 ls2
SYNOPSIS
ls2 [
DESCRIPTION
Same as
, but with decimal precision in temperature fields.
·
Indoor Unit status line with Celsius temperature scale
01234567890123456789012345678901234567890
L1.102 ON 16.9C 27.0C High Cool OK - 0
·
Indoor Unit status line with Fahrenheit temperature scale
0123456789012345678901234567890123456789012
L1.102 ON 062.4F 080.6F High Cool OK - 0
Field
Position in string
Values
Celsius
Fahrenheit
UID
0-5
Ln.XYY
On/Off
7-9
ON
or
OFF
Set Temperature
11-14
11-15
nnC
or
nnnF
Room Temperature
17-20
18-22
nnC
or
nnnF
Fan Speed
23-26
25-28
VLow Low
_
Med
_
High Top
_
Auto
Operation Mode
28-31
30-33
Cool Heat Fan
_
Dry
_
Auto
Indoor Failure Code
33-36
35-38
OK
- no failure, else indoor Failure Code
Filter Sign
38
40
-
or
#
meaning filter sign
Demand
40
42
0
or
1
EXAMPLE
>
ls L2
L2.101 ON 25.7C 27.2C Low Cool OK - 1
L2.102 OFF 20.0C 27.3C High Cool OK - 0
OK
>
ls L2.101
L2.101 ON 25.7C 27.2C Low Cool OK - 1
OK
>
ls
L1.101 ON 25.4C 24.1C Low Cool OK - 1
L1.102 ON 22.1C 23.4C Med Cool OK - 0