28
www.coolautomation.com
CooLinkHub PRM 1.0
© 2017 CoolAutomation
ASCII I/F
L2.101 ON 25.7C 27.2C Low Cool OK - 1
L2.102 OFF 20.0C 27.3C High Cool OK - 0
OK
5.3.18 query
SYNOPSIS
query <
> <o|m|f|t|h|e|a|s>
DESCRIPTION
Query one of the status parameters for given indoor unit. (<
> parameter references a single
indoor unit). Query result is printed as alpha-numeric value according to the table below.
Query parameter
Status parameter
Value
o
On/Off
0
- Off,
1
- On
m
Operation Mode
0
- Cool
1
- Heat
2
- Auto
3
- Dry
4
- Haux
5
- Fan
f
Fan Speed
0
- Low
1
- Medium
2
- High
3
- Auto
4
- Top
t
Set Temperature
Natural number
e
Failure Code
0
- No failure,
otherwise failure code
a
Ambient Temperature
Natural number
h
Set Temperature with 0.01º
Precision
Fractal number
s
Louver Position
0
- No Louver Control
a
- auto (swing)
h
- horizontal
3
- 30º
4
- 45º
6
- 60º
v
- vertical
x
- stop (swing)
EXAMPLE