13
www.coolautomation.com
CooLinkHub PRM 1.0
© 2017 CoolAutomation
ASCII I/F
106
Line Init In Progress...
Line initialization is in process
107
Line Error
Error(s) on the HVAC line
108
Feed Disabled
Indoor unit can't receive ambient temperature from
CooLinkHub
109
Line Queue Full
Commands queue of the Line is full
150
HDL Not Initialized
HDL line was not defined or Ethernet link is down
151
HDL DB Overflow
HDL Data Base is full, can't add new configuration
152
HDL Eth Disabled
HDL over Ethernet is disabled
200
UID Not Found
Specified indoor unit not found in Data Base
201
Strict UID Not Found
Specified indoor unit by not found in Data Base
202
Indoor Removed
Indoor unit removed from Data Base
203
DB Overflow
Indoor units Data Base is full
204
Group DB Overflow
Group Data Base is full
205
VA DB Overflow
Virtual address Data Base is full
206
FDB5 Overflow
Properties Data Base is full
207
Incorrect Unit Class
Wrong class of the HVAC unit
250
Link DB Overflow
Link Data Base is full
251
No CoolLinkHub Line
CoolLinkHub line is not defined
252
Auto Visibility Failed
There was an error of visibility during link creation
253
Link already exists
Device already linked
307
KNX DB Overflow
KNX Data Base is full
309
KNX Not Connected
No communication with KNX extender
310
KNX Line Not Started
KNX line not defined
450
Luxom Disabled
Luxom module not enabled
451
Luxom DB Overflow
Luxom Data Base is full
452
Luxom Not Initialized
Luxom module not initialized
5.1.3
UID
UID is used to identify indoor unit or a set of indoor units. UID has the following format:
Line
dot
Indoor number
L<n>
.
X
YY
·
Line is a CooLinkHub HVAC Line number like
L1
,
L2
, ...
L*
- means "any line". To provide backward
compatibility with CoolMaster and CooLink devices, Line number can be omitted from the UID.