Document 9850-000224-00 EG2
Set Up Instructions
Configuration
iCAN Device Number
The EG2 is supplied with a iCANnet Device number with Segment number 255 and a
node number in the range 1-255. Both Segment and Node number can be changed using
iCANsoft.
Factory Default IP settings
IP Address 192.168.0.100
•
Mask
255.255.255.0
•
DHCP
Off
•
Note
the EG2 default settings are to use
a fixed IP address of 192.168.0.100. Any
device used to communicate with the
EG2 will need to be located within the
192.168.0.x subnet.
Power up
The EG2 takes approximately 60 seconds to be ready for use once power is applied.
Wait for the Green CAN LED to flash slowly.
The Green Power LED will double flash continuously while EG2 is on.
If Ethernet is connected the Link and Data LEDs will indicate successful connection.
Setting the IP address
The factory set IP Address can be changed using the iCANnet connection or using a
computer connected directly to the Ethernet port.
Changing with iCANnet
Connect to the iCAN network a computer running iCANsoft using a Cooper Controls PC
Node. Search the network and load the EG2 into iCANsoft.
Go the Ethernet tab. Either the Default settings can be applied or other settings can be applied.
Select OK or Apply to download the changes to the EG2.