UL 924 Remote Relay Unit

NOTICE:

 Designed for indoor installation and use only. Dry location rated.

NOTICE:

 All new wiring must be fully verified before applying power.

NOTICE:

 Do not let power supply cords touch hot surfaces

NOTICE:

 Do not mount near gas or electric heaters

NOTICE:

 Equipment should be mounted in locations and heights where it will not readily be subjected to tampering by unauthorized 

personnel

NOTICE:

 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition

NOTICE: 

Do not use this equipment for other than intended use

Installation Instructions 

UL 924 Remote Relay Unit

  WARNING

Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be per-

formed by a qualified electrician. This product must be installed in accordance with the applicable installation code by a per-

son familiar with the construction and operation of the product and hazards involved. For continued protection against shock 

hazard replace all covers and guards after field wiring is completed.

Risk of Fire and Electric Shock- Before installing or performing any service, the power MUST be  

turned OFF. All installations should be in compliance with the National Electric Code and all state  

and local codes.

Risk of Burn- Disconnect power and allow product to cool before handling or servicing.

Risk of Personal Injury- Due to sharp edges, handle with care.

Failure to comply with these instructions may result in death, serious bodily injury and property damage.

DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the 

improper, careless, or negligent installation, handling or use of this product.  
IMPORTANT: 

Read carefully before installing product. Retain for future reference.

  

NOTICE: 

Product may become damaged and/or unstable if not installed properly.

 

Note: 

Specifications and dimensions subject to change without notice.

ATTENTION Receiving Department: 

Note actual product description of any shortage or noticeable damage on delivery receipt. File claim 

for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All damaged material, 

complete with original packing must be retained.

Model # RRU-UNV

Summary of Contents for RRU-UNV

Page 1: ...r field wiring is completed Risk of Fire and Electric Shock Before installing or performing any service the power MUST be turned OFF All installations should be in compliance with the National Electric Code and all state and local codes Risk of Burn Disconnect power and allow product to cool before handling or servicing Risk of Personal Injury Due to sharp edges handle with care Failure to comply ...

Page 2: ... 5 12 AWG Hot 120 277 VAC Relay Neutral White 2 18 AWG 1 18 AWG To Normal Power Source C To override ON Connect dry contact between on override and 24 VDC When contact closes all relays are forced ON Contacts will close when normal power is lost Connector on Motherboard RRU UNV iLumin SC Panels ote N The iLumin SC panel must be fed an emergency power source in order for the RRU UNV to operate prop...

Page 3: ...evious screen Control Wiring For Emergency Panel congurations ensure the iLumin SC panel is fed from an emergency power source The RRU UNVprovides a dry contact maintained closure to the switch input 1 or switch input 2 terminal on the iLumin SC panel input card Emergency actions can be programmed from the iLumin SC panel on board user interface Contact Closure NC C Relay To Normal Power Source C ...

Page 4: ...on et un usage à l intérieur Produit conçu pour un emplacement sec AVIS Il faut entièrement vérifier tous les nouveaux câblages avant la mise sous tension AVIS Évitez tout contact des cordons d alimentation avec les surfaces chaudes AVIS N installez pas près d un chauffage électrique ou à gaz AVIS L équipement doit être monté dans des endroits et à des hauteurs où il ne pourra pas être modifié par...

Page 5: ... On Éteint Off NC C Sous tension 120 VCA Noir Sous tension 277 VCA Orange Relais Neutre Blanc Vers l alimentation régulière C Pour que la priorité soit ACTIVÉE Connectez le contact sec entre le raccord de priorité activé et 24 VCC Lorsque le contact se ferme tous les relais sont ALLUMÉS de force Les contacts se ferment lorsque l alimentation normale est coupée Connecteur sur la carte mère 4 14 AWG...

Page 6: ...ppuyez sur ESC pour enregistrer tous les changements et revenir à l écran précédent Câblage des commandes Pour les configurations de panneaux d urgence assurez vous que le panneau iLumin SC est alimenté par une alimentation de secours Le RRU 1assure un contact sec sur la borne de l interrupteur d entrée 1 ou de l interrupteurd entrée 2 sur la carte d entrée du panneau iLumin SC Les actions d urgen...

Page 7: ...ponsabilidad por daños o pérdidas de ningún tipo que puedan surgir por la instalación manipulación o uso inadecuado descuidado o negligente de este producto IMPORTANTE Lea atentamente antes de instalar la luminaria Conserve estas instrucciones para tenerlas como referencia futura AVISO La luminaria puede dañarse y o ser inestable si no se instala correctamente Nota Las especificaciones y dimension...

Page 8: ...able blanco Conecte el cable vivo al cable de color ENCENDIDO APAGADO NC C Vivo 120 VAC Negro Vivo 277 VAC Naranja Relé Neutro Blanco A la fuente de energía normal C Para anular ENCENDIDO Conecte el contacto seco entre ENCENDIDO anulado y 24 VDC Cuando se cierren todos los contactos todos los relés se forzarán a ENCENDIDO Los contactos se cerrarán cuando se pierda la energía normal Conector a la p...

Page 9: ...presione el botón ESC para guardar todos los cambios y regresar a la pantalla anterior Cableado de control Para configurar el panel de emergencia asegúrese de que una fuente de energía de emergencia alimente al panel iLumin SC La unidad RRU 1suministra un cierre mantenido del contacto seco al terminal de la entrada de interruptor 1 o entrada de interruptor 2 en la tarjeta de entrada del panel iLum...

Page 10: ...vent être modifiées sans préavis La disponibilidad de productos las especificaciones y los cumplimientos están sujetos a cambio sin previo aviso Cooper Lighting Solutions 1121 Highway 74 South Peachtree City GA 30269 P 770 486 4800 www cooperlighting com 2020 Cooper Lighting Solutions All Rights Reserved Tous droits réservés Todos los derechos reservados Publication No IB053058ML October 2019 Warr...

Reviews: