Calibrating All Sensors in an Area
1: Bring the mobile device within range (within 60 feet) of any provisioned WaveLinx Lite device in the desired area.
2: Ensure that the mobile device Bluetooth is turned on, and then open the WaveLinx Lite Mobile Application.
3: In the site list, select a site.
4: In the area list, select the desired area. After a short delay, verify that the area shows that the mobile application is connected to the network.
Tap on the icon if it is necessary to refresh the connection.
5: Tap ‘Daylight’ to open the daylight set list.
6: Tap the ‘Calibrate All’ option to open the group calibration screen.
7: In the calibration screen, optionally, enter the surface light reading using a light meter for reference. This allows current reading fields to
approximate more closely what the light level is at the desired surface. This will have no effect on the calibrated level other than for reviewing
or displaying the current reading. If entering the reading, select either lux or foot-candles to match what was used on the light meter.
8: Use the screen controls to change each ‘Closed Loop Set’ light level:
•
For outdoor applications calibrated at night: Recommended to set all closed loop sets to 100% light level.
•
For indoor applications: Use the light level adjustment controls to adjust each fixture to the desired light level.
Repeat for all sensor sets in the area, scrolling if necessary. Lighting should respond and assume the defined light level.
9: At the bottom of the calibration screen, tap on the calibrate button. The current light level of each of the affected sensor will then be stored
as the target 100% light level.
10. The mobile application will show whether calibration was successful for all devices. Devices that show a checkmark ‘ ’ indicate
successful transmission. Devices that show a refresh icon ‘ ’ indicate a transmission failure. Tap the refresh icon to resend the settings to
that device until all devices show successful transmission.
IMPORTANT:
Before calibration, review the specific device type recommendations for when daylight calibration
should be performed. See “WaveLinx Lite Device Reference Sheets” on page 5 to locate recommendations for the
device being calibrated.
Select the site
Select the area
Tap ‘Daylight’
Verify network
connection
Connected
Not connected
Tap ‘Calibrate
All’