9: In the mobile application, navigate to the device details, ‘Daylight Sensor’ page and enter the ‘Daylight Factor Sensitivity’ value from the
calculations. Tap ‘Save’ and then ‘Confirm’ in the warning message popup.
10: In the same screen, place the daylight sensor back into test mode.
11: Shine a flashlight into the sensor lens until the light turns OFF (30 seconds to 1 minute). Turn the flashlight OFF and wait for the light to turn
back ON. (light should respond after approximately 30 seconds).
•
If the light responds properly to this test: Adjustment is complete.
Turn off test mode.
•
If the light remains OFF after the flashlight is removed, increase the Daylight Factor Sensitivity by 20% and then repeat step 11 test. If the
light responds correctly, adjustment is complete.
Turn off test mode
. (If the light still does not respond ON, contact technical support.)
Repeat this procedure for every fixture that is exhibiting the failure to turn ON behavior.
Note
: Adjusting one fixture may cause other fixtures adjacent to that fixture to exhibit the problem. If this occurs, follow these procedures for the
affected fixtures.
Tap ‘Confirm’’
Tap ‘Save’
Disable daylighting
for test device
Turn ON Test Mode
Once done, turn
OFF Test mode