P82623 F
Sheet 1 of 6
273 Branchport Avenue
Long Branch, NJ 07740
(800)
631-2148
(USA)
Thank you for using our products.
(800) 397-5777 (CANADA)
www.coopernotification.com
INSTALLATION INSTRUCTIONS
AMT MULTITONE APPLIANCES
AMT-12/24
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
AMT Multitone Appliances are UL Listed under Standard 464 for Audible Signal Appliances for Fire Protective Service and for General Signaling Service.
They are also ULC Listed under Standard CAN/ULC-S525-07 for Audible Signal Appliances for Fire Alarm Systems. They are listed for both indoor and
outdoor use with the backboxes specified in these instructions. (See Mounting Options A,B,C,D,E,F,G). Cooper Notification's AMT Appliances are
unique multitone alarm appliances with separate input terminals for each sound. They are the ideal choice for Halon Protection Systems and emergency
signaling systems where distinctive multiple alarm conditions are required. Eight groups of three self-prioritized sound outputs are provided with
separate electrically isolated input terminals for each sound (see Table 2 and 5 for sound selections). Sound output can be field set to provide either
HIGH (HI) dBA or STANDARD (STD) dBA sound output level. AMT Multitone Appliances can be field set for either 12VDC or 24VDC operation and are
designed for use with either filtered or unfiltered Full-Wave-Rectified (FWF) input voltage. All inputs are polarized for compatibility with standard reverse
supervision of circuit wiring by Fire Alarm Control Panel (FACP).
NOTE:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY
OR DEATH TO YOU AND/OR OTHERS.
NOTE:
All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems, CAN/ULC-S524 and
the Canadian Electrical Code, Part 1. Final acceptance is subject to authorities having jurisdiction.
WARNING: THE AMT MULTITONE APPLIANCES MUST BE FIELD SET TO THE DESIRED INPUT VOLTAGE, dBA SOUND OUTPUT LEVEL
AND ALARM TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR
POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE
AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
SPECIFICATIONS:
Table 1: dBA Ratings for AMT Multitone Signal
Typical
Anechoic
dBA at 10 Feet per
CAN/ULC S525-07
Rated Reverberant dBA
At 10 Feet Per UL 464
Tone At
Nominal
At
Minimum At
Nominal
Input Voltage
Input Voltage
Input Voltage
HI STD HI STD HI STD
Horn
99 93 88 79 88 82
Bell
93 88 82 75 85 79
March
Time
Horn
98 92 85 79 88 82
Code-3 Horn * (ANSI S3.41 Temporal Pattern)
99
93
85
75
85
79
Code-3 Tone * (ANSI S3.41 Temporal Pattern)
95
89
85
79
88
82
Slow
Whoop
99 94 82 75 85 79
Siren
97 92 82 75 82 75
HI/LO
93 85 82 75 85 79
Vibrating
Chimes
89 83 79 73 82 75
* - For ULC applications, only Code 3 Horn and Code 3 Tone are required to meet the ULC minimum of 85 dBA and the audible signal temporal
pattern mandated by the National Building Code of Canada.
Copyright 2015 Cooper Wheelock Inc., dba Cooper Notification. All rights reserved.