Copyright 2009 Cooper Wheelock Inc., dba Cooper Notification. All rights reserved.
P83933 T
Sheet 1 of 4
273 Branchport Avenue
Thank you for using our products.
Long Branch, NJ 07740
(800)
631-2148
INSTALLATION
INSTRUCTIONS
www.coopernotification.com
SERIES
ET70-24MCW,
ET90-24MCW
MULTI-CANDELA LOW PROFILE SPEAKER STROBE
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Series ET70-24MCW and ET90-24MCW Multi-Candela Low Profile Speaker Strobe is UL Listed under Standard 1971 for (Signaling Devices for the Hearing
Impaired) for indoor fire protection service. Models with amber, blue, green or red lens are UL Listed under Standard UL1638 (Visual Signaling Appliance) for Private
Mode Emergency and General Utility Signaling. The speaker strobes are designed for multiple power requirements with high dBA output at each power tap and offer a
choice of field selectable taps, 1/8W to 8W for either 25.0VRMS or 70.0VRMS audio systems. The Low Profile design incorporates a high efficiency speaker for
maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved audibility.
These models provide four selectable light output intensities in one unit and incorporate a speaker mounting plate attached to the speaker for ease of installation. The
Low Profile Speaker Strobe can provide a non-synchronized strobe appliance when connected directly to a fire alarm control panel (FACP), or provide a synchronized
strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Cooper Notification power supplies. The strobe uses a xenon
flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling. These models are Listed
for
indoor use, wall mount only
with the backboxes specified in these instructions (see wiring and mounting information).
NOTE:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING
INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL Listed Models and Ratings
Speaker
Strobe
Models
Voltage
dBA at 10 Feet
(Rated Watts)
Regulated
Voltage
Voltage
Range
Candela Mounting
(VRMS)
Options
1/8 1/4 1/2 1 2 4 8 (VDC/VRMS) (VDC/VRMS)
ET70-24MCW 25/70
75 78 81 84 87 90 93
24
16.0-33.0
15/30/75/110
A,B
ET90-24MCW 25/70
75 78 81 84 87 90 93
24
16.0-33.0
15/30/75/110
A,B
NOTES:
1.
The strobe will produce 1 flash per second over the "Regulated Voltage" range.
2.
Strobes with clear and amber lens meet the required light distribution patterns defined in UL 1971.
3.
These models are UL Listed for indoor use with a temperature range of +32
F to +120
F (0
C to +49
C) and maximum humidity of 85% RH. The effect of
shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and is not subjected to
misuse or abuse.
4.
Candela ratings listed in Table 1 are for clear lens. Derate approximately 25% for amber lens, 55% for green lens, 70% for blue lens and 80% for red lens.
5.
The maximum supervision voltage is 33 volts DC.
6.
Frequency range of speakers is 400-4000Hz.
CAUTION:
Always operate audio amplifiers and speakers within their specified ratings. Excessive input may distort sound quality and may damage audio
equipment. Do not exceed 100% of speaker input voltage per UL 1480. Improper input voltage can damage speaker. If distortion is heard, check for clipping of the
audio appliance with an oscilloscope and reduce the amplifier input level or gain level to eliminate any clipping.
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 2: UL Current Ratings with Strobe Only
Maximum RMS Current (AMPS)
UL
Voltage
15cd 30cd 75cd 110cd
DC
16-33VDC
0.060 0.092 0.165 0.220
FWR
16-33VRMS
0.102 0.155 0.253 0.347
When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of
strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety
factors.
NOTE:
The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
CAUTION:
These strobes are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as “Regulated.”
These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation
instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
WARNING: THESE STROBES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING
FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.