CEAG Notlichtsysteme GmbH
23
Construction and Function
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
** Loopresistor
* Terminal without function
Connections F3 Modul
Switch for loop resistance
The F3 - remote indicating unit con-
tains a switch for loop resistance.
The right figure shows the printed
board which includes a marking
stating the switch settings depen-
ding on the system.
Switch for loop
resistance
left: ZB-S / AT-S
+
right: ZB 96
CG 2000
View on the F3 module after
opening the front panel.
Switch setting on the left side
for AT-S
+
/ZB-S/CG2000 system.
Connection of a remote switch
Connections are made as per figure (single-line diagram) as well as field
installation diagrams and drawings.
The CEAG F3 remote switch is powered via the 24-V voltage supply
system of CEAG sytems.
Attention!
Do not use an external 24-V voltage supply!
Note:
Observe national rules and regulations governing the indi-
cating and signalling behavior when using a remote switch or a
remote indicator for emergency lighting systems.
Observe the instruc-tions in the Technical Documentation as
provided by the manufacturer of the CEAG F3 remote indicator.
4.4.4 F3 remote indication
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
AT-S+
Terminals
F3 Module
Terminals
2,5 mm²
starr/flexibel
Terminals
AT-S+
C0
C0
12
12
12
14
12
14
22
22
22
24
22
24
**
32
**
32
32
34
32
34
S1
S1
S1
S1
S2
S2
S2
S2
+24V
+24V
+24V
+24V
*
-24V
*
-24V
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
AT-S+
Terminals
F3 Module
Terminals
2,5 mm²
starr/flexibel
Terminals
AT-S+
C0
C0
12
12
12
14
12
14
22
22
22
24
22
24
32
32
32
34
32
34
S1
S1
S1
S1
S2
S2
S2
S2
+24V
+24V
+24V
+24V
-24V
-24V
F3 Fernanzeige Wandmontage
F3 Module Wallmounting
Connecting F3 Module to AT-S+
F3 Fernanzeige UP-Montage
F3 Fernanzeige UP-Montage - F3 Module UP-Mounting
Connecting F3 Module to AT-S+
Anschluss F3 Fernanzeige an AT-S+
Anschluss F3 Fernanzeige an AT-S+
R=1K
Ω
R=1K
Ω
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
AT-S+
Terminals
F3 Module
Terminals
2,5 mm²
starr/flexibel
Terminals
AT-S+
C0
C0
12
12
12
14
12
14
22
22
22
24
22
24
**
32
**
32
32
34
32
34
S1
S1
S1
S1
S2
S2
S2
S2
+24V
+24V
+24V
+24V
*
-24V
*
-24V
Klemmen
F3 Fernanzeige
Klemmen
2,5 mm²
starr/flexibel
Klemmen
AT-S+
Terminals
F3 Module
Terminals
2,5 mm²
starr/flexibel
Terminals
AT-S+
C0
C0
12
12
12
14
12
14
22
22
22
24
22
24
32
32
32
34
32
34
S1
S1
S1
S1
S2
S2
S2
S2
+24V
+24V
+24V
+24V
-24V
-24V
F3 Fernanzeige Wandmontage
F3 Module Wallmounting
Connecting F3 Module to AT-S+
F3 Fernanzeige UP-Montage
F3 Fernanzeige UP-Montage - F3 Module UP-Mounting
Connecting F3 Module to AT-S+
Anschluss F3 Fernanzeige an AT-S+
Anschluss F3 Fernanzeige an AT-S+
R=1K
Ω
R=1K
Ω