P84450 F
Sheet 2 of 4
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING
FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE
VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES. THE
MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
CAUTION:
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE
SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR
COOPER WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF
ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT
IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WIRING AND MOUNTING INFORMATION:
CAUTION:
The following figures (A-F) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If
these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
CAUTION:
Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Wheelock recommends use of the largest backbox
option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the
product from wiring.
FLUSH MOUNTING
A
STD. SINGLE-GANG
BACKBOX 2" DEEP
#6-32 SCREWS
STROBE MOUNTING
PLATE (SMP)
BEAUTY PLATE
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 4 4
FLUSH OR SURFACE MOUNT
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 4 4
4" SQ. X 1-1/2" DEEP BACKBOX
OR 100m X 37.5mm
EUROPEAN BACKBOX
STROBE MOUNTING
PLATE (SMP)
B
#8-32 SCREWS
BEAUTY PLATE
FLUSH OR SURFACE MOUNT
C
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 4 4
DOUBLE-GANG X 2-1/4"
DEEP BACKBOX
#6-32 SCREWS
STROBE MOUNTING
PLATE (SMP)
BEAUTY PLATE
#8-32 SCREWS
D
SURFACE MOUNTING
SHALLOW SURFACE
BACKBOX (SHBB)
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
4 4 4 4
STROBE MOUNTING
PLATE (SMP)
BEAUTY PLATE
E
FLUSH MOUNTING
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8 8 8 8
STANDARD 4" X 2-1/8"
DEEP BACKBOX
APPLIANCE
SURFACE MOUNTING
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
8 8 8 8
APPLIANCE
BACKBOX (SBL-2)
F